background image

 

Chapter 3: Programming 

 

SIGA-REL Technical Reference Manual 

37 

Table 17: SIGA-REL labels and messages 

Device type 

Example 
address [1] 

Label 

Message 

Model 

Monitor 

0207 

Abort 

Abort 

SIGA-REL 

Pull 

0208 

Manual 

Manual 

SIGA-REL 

DoorControl 

0209 

Release_1 

Release_1 

SIGA-REL 

None 

0210 

Release_2 

Release_2 

SIGA-REL 

DoorControl 

0211 

Prerelease_1 

Prerelease_1 

SIGA-REL 

None 

0212 

Prerelease_2 

Prerelease_2 

SIGA-REL 

[1] These addresses illustrate that the SIGA-REL should occupy six consecutive addresses. The 
actual addresses in your system may differ. 

Creating an abort confirmation LED 

WARNING: 

If the abort circuit is shorted, the system interprets this as a manual 

abort. This would prevent release of the fire suppression agent in the event of an 
actual fire alarm. 

To guarantee supervision of the manual abort circuit, we suggest that you 
program an LED to light when the abort circuit is activated. This has the benefit 
of providing a clear visual indication to untrained site personnel that the abort 
circuit has been compromised due to a short circuit. 

Programming an AND group 

AND groups function as counting groups. For more information about 
programming AND groups, see the 

EST2 System Programming Manual

 and the 

2-SDU Help

Every device contained in each (SIGA-REL) AND group must include a rule with 
an output statement like the one in [ALARM1]. See Figure 17 for the details. 

Note:

 To comply with NFPA 72, you must program an AND Group with at least 

two smoke detectors and a minimum activation count of 2. The smoke detectors 
must have their Primary and Alternate Verification properties set to None (verified 
smoke detectors are not allowed). 

Reconciling the Signature map 

Do not use the Accept Actual function in the Signature Series mapping tool. 
Accepted devices may appear as two devices in the SDC database and corrupt 

Содержание SIGA-REL Technical

Страница 1: ...SIGA REL Technical Reference Manual P N 387348 EN REV 007 ISS 22SEP17...

Страница 2: ...ed and used in accordance with the instruction manual may cause harmful interference to radio communications You are cautioned that any changes or modifications not expressly approved by the party res...

Страница 3: ...Chapter 2 Installation 19 Mounting the SIGA REL 20 Setting abort mode and delay times 22 Reading the LEDs 24 Wiring the SIGA REL 25 Warning notice placards 29 Chapter 3 Programming 33 Programming the...

Страница 4: ...accordance with this manual applicable codes and the instructions of the authority having jurisdiction is mandatory While every precaution has been taken during the preparation of this manual to ensu...

Страница 5: ...oid in order to prevent the injury or loss of life Caution Caution messages advise you of possible equipment damage They tell you which actions to take or to avoid in order to prevent the damage Note...

Страница 6: ...documentation Signature Series Intelligent Smoke and Heat Detectors Applications Bulletin P N 270145 Signature Series Component Installation Manual P N 270497 Serial Number Log Book P N 270267 EST Pu...

Страница 7: ...ive Signaling Systems EST2 UL 864 9th Edition Standard for Control Units for Fire Protective Signaling Systems EST3 UL 864 9th Edition Standard for Control Units and Accessories for Fire Alarm Systems...

Страница 8: ...vi SIGA REL Technical Reference Manual...

Страница 9: ...EL fits into a fire alarm system and how it behaves during fire alarms Content Introducing the SIGA REL 3 Description 3 Features 4 Fire suppression systems 4 Sprinkler systems 4 Automatic fire extingu...

Страница 10: ...r 1 Product design 2 SIGA REL Technical Reference Manual Automatic fire extinguishing systems 14 Fire suppression application 15 Release sequences 16 Automatic release sequence 16 Manual release seque...

Страница 11: ...ed abort circuit for a normally open abort switch Figure 1 SIGA REL Releasing Module The SIGA REL controls operations for deluge preaction and automatic fire extinguishing systems The release circuits...

Страница 12: ...ease valves See Table 4 in the topic Compatible panels and devices Table 1 FM requirements for deluge and preaction systems Specification Value Standby operation 90 hours Alarm operation 10 minutes NF...

Страница 13: ...fire extinguishing systems Automatic fire extinguishing systems automatically detect and extinguish fires They require no manual input because detectors automatically activate releasing solenoids or...

Страница 14: ...ontrol panels SIGA RELThe SIGA REL must be installed in an enclosure dedicated to the releasing system No other devices may be installed in the enclosure You can install the SIGA REL in any of the fol...

Страница 15: ...trol panel documentation for a list of compatible appliances Note that the SIGA REL is not designed to generate an NFPA 72 standard alarm evacuation signal and does not meet UL 864 requirements for an...

Страница 16: ...momentary action abort stations The abort station controls only the SIGA REL to which it is connected Abort stations must be listed with the appropriate agencies in your area See the heading Listing a...

Страница 17: ...facturer Model A Skinner LV2LBX25 B ASCO T8210A107 R8210A107 8210A107 D ASCO 8210G207 HV2648571 HV2648581 E Skinner 73218BN4UNLVNOC111C2 73212BN4TN00N0C111C2 F Skinner 73212BN4TNLVNOC322C2 G Skinner 7...

Страница 18: ...4 Valves per circuit Line resistance End of line device Supervision UL rating Ground fault impedance 2 A at 24 VDC max 1 2 A at 24 VDC max 1 4 valves max See Table 8 47 k resistor Open short and grou...

Страница 19: ...o 93 noncondensing 1 Riser current The total current of the prerelease and release circuits is limited to 3 83 A This is the power riser maximum input current of 4 A minus 170 mA Table 7 Power riser T...

Страница 20: ...rd alarm evacuation signal and does not meet UL 864 requirements for audible alarm notification circuits intended for evacuation Notification zones must include additional NACs and appliances capable...

Страница 21: ...d release signals The alert tone sounds at 15 pulses per minute the prerelease tone at 60 pulses per minute The release tone is a steady tone Prerelease circuit 2 supports visual notification applianc...

Страница 22: ...on of the SIGA REL with an automatic extinguishing system Signature loop controller Releasing Module Fire alarm control panel RELA EOL Preaction or deluge system 1 M Class A wiring required for FM app...

Страница 23: ...gure 4 is a typical application for the Releasing Module Figure 4 Typical computer room application Signature loop controller Releasing Module SD Fire alarm control panel Signature Series smoke detect...

Страница 24: ...system Figure 5 explains the automatic release sequence Note EST2 systems do not support matrix groups See Chapter 3 Programming on page 33 for details on AND group rules To create AND groups see the...

Страница 25: ...atic delay timer expires the horn circuit changes to the release tone steady 2 A detector in the protected area signals a second alarm and meets the AND group conditions After a ten second delay the a...

Страница 26: ...nual delay timer Prerelease circuits Selectable manual delay time 0 to 30 seconds 1 3 4 Time line see details below 2 1 An active manual release station disables automatic operation and the abort func...

Страница 27: ...A REL When you install the SIGA REL be sure to follow agency and local requirements along with the instructions in this manual Content Mounting the SIGA REL 20 Setting abort mode and delay times 22 Ch...

Страница 28: ...REL to the designated mounting holes in the MFC A Figure 7 and Figure 8 2 Secure the SIGA REL to the MFC A using the screws and washers provided 3 Run the wiring from the SIGA REL to the fire suppress...

Страница 29: ...t MFC A Conduit knockout Conduit knockout 6 Flat washers 6 32 Self tapping screws Releasing Module Mounting space Mounting hole diameter is 0 125 in or 3 175 mm Interior surface of enclosure Interior...

Страница 30: ...s To be recognized as valid the abort must be active when the second alarm is received When the abort is restored the release occurs with the expiration of the abort delay timer set for 10 seconds If...

Страница 31: ...e settings Time delay SW3 SW4 No delay 0 0 10 seconds Default 0 1 20 seconds 1 0 30 seconds 1 1 Table 13 Automatic delay time settings Time delay SW5 SW6 SW7 10 seconds 0 0 0 20 seconds 0 0 1 30 secon...

Страница 32: ...hrough DS7 Figure 11 SIGA REL LEDs Table 15 SIGA REL LEDs LED Color Pattern Function DS1 Red Flashing Data alarm conditions DS2 Green Flashing Data normal conditions DS3 Red Steady Alarm DS4 Green Ste...

Страница 33: ...nsure that you are using a compatible power supply as listed in the topic Compatible panels and devices on page 6 Wire the SIGA REL according to Figure 13 If your application requires supervision of t...

Страница 34: ...3 2 1 Releasing Module TB1 4 3 2 1 TB4 _ _ 3 2 1 4 TB5 3 2 1 4 _ _ 3 2 1 4 1 2 3 4 RELA EOL Zone relay output Class E 10 In Out _ _ _ 24 VDC in 24 VDC out Prerelease circuit 2 steady 8 15 2 5 Prerele...

Страница 35: ...ted source If nonpower limited maintain 1 4 inch 6 4 mm separation Otherwise use FPL FPLR or FPLP in accordance with the National Electric Code NEC 11 Listed service disconnect station Must be rated f...

Страница 36: ...isconnect switch RELA SRV 1 DATA OUT to next device Releasing Module TB4 47 k EOLR 7 8 1 2 3 4 DATA IN from previous device Model CT1 Device type Supervisory Personality 3 Active B Text 1 REL1 RELEASE...

Страница 37: ...gs their locations and their importance Enforce compliance with these warnings during all installation testing and service procedures Active Normal TB4 1 2 3 4 TB5 1 2 3 4 RELA EOL RELA EOL Horn or st...

Страница 38: ...ing notice WARNING Disconnect all wiring on TB4 of the Releasing Module release circuits 1 and 2 during system service Disabled points will not prevent activation of the release circuits Failure to fo...

Страница 39: ...g occupants must be notified prior to any system test or service All releasing circuits must be manually disconnected prior to any system test or service All releasing circuits must be returned to the...

Страница 40: ...Chapter 2 Installation 32 SIGA REL Technical Reference Manual...

Страница 41: ...ng the SIGA REL to the database 35 Creating an abort confirmation LED 37 Programming an AND group 37 Reconciling the Signature map 37 Writing rules for the SIGA REL 38 Programming the SIGA REL in the...

Страница 42: ...Step 9 Indicate active prerelease and release circuits 48 Step 10 Create a drill prerelease response 48 Step 11 Retrieve the loop data from the SLIC 49 Step 12 Reconcile the actual and expected data 4...

Страница 43: ...GA REL is for the abort switch and manual release switch circuits the second for the two release circuits and the third for the two prerelease circuits Note You cannot have more than 10 SIGA REL modul...

Страница 44: ...k Commit Expected 10 Close all Signature Series mapping tool dialog boxes and windows 11 Perform a Signature Series conversion and download the database to the panel Table 16 SIGA REL configuration se...

Страница 45: ...we suggest that you program an LED to light when the abort circuit is activated This has the benefit of providing a clear visual indication to untrained site personnel that the abort circuit has been...

Страница 46: ...es match the labels assigned in the Object Configuration LED1 and LED2 require the addition of an LED module to the MCM Configuration Make sure that the labels for the LEDs match the labels assigned t...

Страница 47: ...first SIGA REL is for the abort switch and manual release switch circuits the second for the two release circuits and the third for the two prerelease circuits Note You cannot have more than 10 SIGA...

Страница 48: ...ailable address the prerelease circuit and click Accept Actual 10 Close all Signature Series mapping tool dialog boxes and windows 11 Perform a Signature Series conversion and download the database to...

Страница 49: ...ircuit may accidentally activate for maintenance events AND groups function as counting groups matrix groups function as counting zones For more information about programming AND groups and matrix gro...

Страница 50: ...igned to them in the Object Configuration AND GROUP RELEASE rule When the AND_GROUP activates the release circuit is activated after the programmed delay as per the rule MANUAL RELEASE rule If the man...

Страница 51: ...ies to supply 24 VDC to the SIGA REL The SIGA REL mounted in an MFC A enclosure A SIGA CT1 module to supervise the service disconnect switch A SIGA CT2 module to indicate activation of the prerelease...

Страница 52: ...rom beginning to end As a safety precaution disconnect releasing devices from SIGA REL TB4 before downloading setup data to the loop controller The SIGA REL provides only one serial number label When...

Страница 53: ...wing information First address Device type Output Model REL Personality 16 Output B Message text SIGA REL1 A005 and PRERELEASE 1 2 Second address Device type Monitor Personality 0 None Message text SI...

Страница 54: ...e Responses tab click the Response Type arrow and then select Active Caution Do not include the releasing circuits RELEASE 1 2 in this response 6 Click Outputs select the device labeled SIGA REL1 A005...

Страница 55: ...Devices tab and then select the circuit labeled SIGA REL A002 MAN RELEASE 2 Click the Responses tab click the Response Type arrow and then select Active 3 Click Outputs select the device labeled SIGA...

Страница 56: ...nitor 2nd Personality 3 Active B 2nd Text 1 REL1_PREREL 2nd Text 2 CKT_ACTIVE When a circuit is activated the SIGA CT2 module activates a monitor event The corresponding event message identifies which...

Страница 57: ...its current programmed parameters This corrupts the database if you have already entered the device 1 Click the Mapping tab and then click Model 2 Look for a string of at least six RELs marked with re...

Страница 58: ...og select the row that has the REL with the Output device type and marked SIGA REL1 A005 Prerelease 1 2 and then click OK Click Close Step 13 Send the reconciled data to the loop controller Click the...

Страница 59: ...pics that apply to your fire alarm system Content Code requirements for testing 52 System testing 52 Checking your work 52 Testing EST2 systems 53 Testing EST3 systems 53 Testing QuickStart systems 53...

Страница 60: ...connection of releasing solenoids or electric actuators closing of valves other actions or combinations thereof for the specific system for the duration of the fire alarm system testing 7 1 5 4 Testin...

Страница 61: ...des Mapping Device new starts Resets Restarts Testing EST3 systems Allow the system sufficient time to stabilize after the initial startup or download Before you test the system check the Current Stat...

Страница 62: ...ab All LEDs should be off In the 3 SDU choose Tools Signature Series Status Diagnostics then select the Current Status tab All LEDs should be off Note that the Device Supervision LED may take up to 20...

Страница 63: ...and it should go away within minutes Table 21 lists the indications you may see for the SIGA REL on the 2 LCD Table 21 SIGA REL fault messages Device Condition LED 2 LCD message Abort Short Monitor N...

Страница 64: ...e supervision may cause the panel to generate a common trouble active for each SIGA REL circuit This is a normal indication and it should go away within minutes Table 22 lists the indications you may...

Страница 65: ..._2 1 Expanded message TROUBLE SHRT ACT Open Trouble COMMON TRBL ACT Release_2 1 Expanded message TROUBLE OPEN ACT 1 Message requires user programming SIGA REL fault messages on QuickStart panels WARNI...

Страница 66: ...ASE 1 1 Help message TROUBLE OPEN Prerelease_2 Short Trouble Trouble PRERELEASE 2 1 Help message TROUBLE SHRT Open Trouble Trouble PRERELEASE 2 1 Help message TROUBLE OPEN Abort Manual Prerelease_1 Pr...

Страница 67: ...tion 12 automatic extinguishing systems 14 compatible 8 compliance requirements 12 sprinkler systems 13 aborting a manual release 18 Accept Actual command 2 SDU projects 36 37 QS CU projects 49 activa...

Страница 68: ...nting zones See matrix groups creating an abort confirmation LED 37 creating responses in QS CU projects 46 cross zones See AND groups D delay times 22 deluge sprinkler systems 4 13 device types 2 SDU...

Страница 69: ...ication appliances 7 13 O object configuration 2 SDU 35 3 SDU 39 operation of the SIGA REL automatic release sequence 16 manual release sequence 18 P panels compatible 6 personality codes 2 SDU 36 3 S...

Страница 70: ...ease sequence 17 manual release sequence 18 resistance wiring 11 resistors See EOL resistors responses creating in QS CU projects 46 rules 2 SDU 38 3 SDU 41 S separate areas application 15 serial numb...

Страница 71: ...iv system overview 13 system testing 52 T TB1 11 TB2 11 TB3 1 and TB3 2 10 TB3 3 and TB3 4 11 TB4 10 TB5 10 testing checking your work 52 connecting releasing solenoids 52 EST2 53 EST3 53 NFPA 72 req...

Страница 72: ...Index 64 SIGA REL Technical Reference Manual...

Отзывы: