Chapter 3: Programming
SIGA-REL Technical Reference Manual
49
Caution:
Do not include the releasing circuits (RELEASE 1 & 2) in this response.
5. Click Outputs, select the device labeled SIGA-REL1 A005 PRERELEASE 1 &
2, and then click OK.
Step 11: Retrieve the loop data from the SLIC
1. Click Configure, and then click Cabinets.
2. Select the SLIC connected to the SIGA-REL, and then click Configure.
3. Set the Communications Port setting for the COM port used to connect the
service computer to the control panel.
4. Click Retrieve Signature Data.
5. After the upload has finished, click OK.
Step 12: Reconcile the actual and expected data
Caution:
Clicking Accept Actual enters the selected device into the database
with its current programmed parameters. This corrupts the database if you have
already entered the device.
1. Click the Mapping tab, and then click Model.
2. Look for a string of at least six RELs marked with red backgrounds and
double-click the first REL in the string.
3. If the serial number displayed in the Module Properties dialog is not the same
as the serial number shown on the bar code attached to the SIGA-REL, click
Close, and then double-click the next REL in the string.
4. If the serial numbers are the same:
Click Select Expected.
In the Module Selection dialog, select the row that has the REL with the
Monitor device type and marked SIGA-REL1 A001 Abort SW, and then click
OK.
Click Close.
5. Select the next REL, and then click Select Expected.
In the Module Selection dialog, select the row that has the REL with the
Output device type and marked SIGA-REL1 A003 Release 1 & 2, and then
click OK.
Click Close.