SSM-LE Series 

Operations Manual 

Eberle Design Inc. 

Page 9 

and  display  the PROGRAM CARD status screen. The SSM-LE Series

 

will remain in the 

fault mode until the Program Card is correctly seated and the SSM-LE Series

 

is reset by 

the RESET button or the EXTERNAL RESET input. 

3.6 RESET INPUT DETECTION  

Activation of the front panel RESET button or the EXTERNAL RESET input will reset the 
SSM-LE Series

 

from the fault mode and cause the START relay to energize and the 

OUTPUT relay to transfer to the no-fault state. Each activation of the RESET button or 
EXTERNAL RESET input will cause a one time reset input to the unit. A continuously 
activated RESET input will not prevent the SSM-LE Series

 

from monitoring any fault 

condition and/or transferring the OUTPUT relay contacts to the fault position. This function 
prevents the Cabinet Assembly from being operated with the monitor unit disabled due to a 
faulty RESET button or EXTERNAL RESET input.  

3.7 INTERNAL DIAGNOSTICS  

The SSM-LE Series

 

is supplied  with a resident series of self-check diagnostic capabilities 

which monitor for correct operation of the SSM-LE  Series

 

both at power-up and 

continuously during operation. When a diagnostic test fails, the SSM-LE Series

 

will enter 

the fault mode, transfer the OUTPUT relay contacts to the Fault position, and illuminate the 
DIAGNOSTIC indicator. A Power Failure will reset the Diagnostic fault state of the monitor 
(see Section 2.4). Due to the nature of these hardware/firmware failures, other fault 
indicators that may be concurrently displayed with the DIAGNOSTIC indicator may not be 
valid.  

3.8 REAL TIME CLOCK / CALENDAR 

A real time clock is provided on the SSM-LE series Signal Monitor to identify each event 
occurrence with the time of day and date. This information is displayed and stored along 
with the event status when the monitor is triggered by an event condition. The real time 
clock is backed-up by a long life lithium energy cell and thus maintains accurate 
timekeeping even during AC+ interruptions. This accuracy should remain within 
approxi

_3 minutes per month.  

The date and month are automatically adjusted for leap years. Daylight Savings Time 
adjustments are made to the time of day on the Sunday specified by the start and end DLS 
parameters. Daylight Savings Time parameters can be made using the EDI 

ECcom

 

software (see SET OPTIONS in the (

EDI ECcom Software Operations Manual

).  

Setting the correct time of day and date is accomplished using the MODE and INC buttons 
on the front panel (see Section 6.5.4) or by using the SET TIME command using the EDI 

ECcom

 software. 

 

 

 

3.9 DISPLAY LED TEST  

The monitor will illuminate all front panel LED and LCD indicators for 500ms when a Reset 
command is issued by the front panel RESET button or EXTERNAL RESET input. This 
function provides a means to check the operation of all front panel indicators. 

3.10 RECURRENT PULSE DETECTION  

This error detection function supplements the normal Conflict, Dual Indication, and Red Fail 
monitoring algorithms for sensing faults which are intermittent or pulsing in nature.  The 
RMS-Engine is designed to filter out short term transients commonly found on the electrical 
service and provide noise immunity against false signal detections.  The Recurrent Pulse 
detection function is designed to respond to fault conditions which are intermittent in nature 
and do not meet the continuous timing requirements of the normal detection algorithms, yet 

Содержание SSM-12LE

Страница 1: ...NS TECHNICAL INFORMATION FOR THE SSM 6LE SSM 6LEip SSM 6LEC SSM 12LE SSM 12LEip and SSM 12LEC SERIES SIGNAL MONITOR REVISION MARCH 2012 pn 888 1216 002 SSM LE Series NEMA TS 1 Enhanced Signal Monitor...

Страница 2: ...INFORMATION OF EBERLE DESIGN INC PUBLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING COPYRIGHT 2012 EDI MAINTENANCE NOTE THIS SIGNAL MONITOR UN...

Страница 3: ...tion 3 Enhanced Features 7 3 1 Hardware Features 7 3 2 Dual Indication Monitoring 7 3 2 1 GY ENABLE Option 8 3 2 2 Walk Disable Option 8 3 3 Minimum Yellow Clearance Monitoring 8 3 4 External Watchdog...

Страница 4: ...TX Indicator 19 6 1 14 PREV FAIL Indicator 19 6 2 Field Status Display 19 6 3 LED Status Display 19 6 3 1 POWER Indicator 19 6 3 2 FAULT Indicator 20 6 3 3 DIAGNOSTIC Indicator 20 6 4 Buttons 20 6 4 1...

Страница 5: ...8 3 EIA 232 Connector 27 8 3 1 EIA 232 Cable to a PC 28 8 4 Ethernet LAN Port 28 8 4 1 Ethernet LAN Cable 28...

Страница 6: ...RE OVERVIEW 1 2 1 LIQUID CRYSTAL STATUS AND FIELD DISPLAY The SSM LE Series uses a Liquid Crystal Display LCD to show monitor status and two icon based LCDs to show field signal channel and fault stat...

Страница 7: ...g either full wave or positive and negative half wave sinusoidal field signal inputs at the specified voltage levels When triggered by the detection of a fault condition which exists longer than the m...

Страница 8: ...reshold value to determine On Off status This differs from conventional standard NEMA operation where the active threshold is picked according to the color of the field signal Once the high and low On...

Страница 9: ...ill be disabled when the RED ENABLE input is not active 2 2 1 RED ENABLE INPUT The RED ENABLE input will be sensed as active by the SSM LE Series when it exceeds the Red Enable Input threshold Section...

Страница 10: ...lt mode transfer the OUTPUT relay contacts to the Fault position and display the CVM status screen When the TRUE low state is absent for less than the CVM No Fault time the SSM LE Series will not tran...

Страница 11: ...and the last component to sense a proper AC LINE operating voltage The AC LINE and AC NEUTRAL inputs are used to generate the internal voltage supplies required to operate the monitor AC NEUTRAL also...

Страница 12: ...ruption The correct fault indications will be displayed upon restoration of AC Line power This EEPROM device requires no battery back up The time of day in the SSM LE Series is stored in a battery bac...

Страница 13: ...he Clearance Fail Fault time 7 4 The Yellow Change interval consists of the duration of time in which the Yellow field signal input is active in a sequence from Green to Yellow to Red When this minimu...

Страница 14: ...A real time clock is provided on the SSM LE series Signal Monitor to identify each event occurrence with the time of day and date This information is displayed and stored along with the event status w...

Страница 15: ...eries will enter the fault mode transfer the Output relay contacts to the Fault position and display the appropriate CONFLICT DUAL INDICATION or RED FAIL status screen along with RP STATUS The unit wi...

Страница 16: ...FYA Overlap phase must be driven by a load switch monitored on channels 9 10 11 12 respectively The SSM LE Series associates channel 1 with 9 channel 3 with 10 channel 5 with 11 and channel 7 with 12...

Страница 17: ...proaches This mode requires that the Controller Unit be capable of remapping the Protected Green Arrow signal driver to the channel 9 10 11 and 12 Yellow load switch inputs The cabinet must be re wire...

Страница 18: ...from the flashing Yellow Arrow 1 3 5 7 to the solid Red Arrow 1 3 5 7 without a minimum clearance time on the solid Yellow Arrow 1 3 5 7 The fault icon will be displayed for the FYAc channel 1 3 5 7 i...

Страница 19: ...vent 4 1 2 CURRENT STATUS S Fault Type the fault type description Field Status the current or latched RYGW field status and RMS voltages Cabinet Temperature the current or latched temperature if the m...

Страница 20: ...the reported configuration 4 1 7 SIGNAL SEQUENCE EVENT LOG The Signal Sequence event log graphically displays all signal states and Red Enable state for up 30 seconds prior to the SSM LE Series fault...

Страница 21: ...fault mode until the Program Card is correctly seated and the SSM LE Series is reset by the RESET button or the EXTERNAL RESET input 5 2 MINIMUM FLASH TIME PROGRAMMING It is recommended that the Mini...

Страница 22: ...2 2 2 5 4 5 CONTROLLER VOLTAGE MONITOR CVM LATCH PROGRAMMING The CVM Latch function is ENABLED by setting the Option switch labeled CVM LATCH to the ON position See Section 2 3 2 1 5 4 6 24VDC MONITOR...

Страница 23: ...w all active field output signals at the time of the CVM fault 6 1 4 24V 1 INDICATOR The 24V 1 indicator will be illuminated when unit detects a 24V 1 fault The Field Status display will show all acti...

Страница 24: ...dicator will be displayed when the EIA 232 or Ethernet port has correctly received a message 6 1 13 TX INDICATOR The Tx indicator will be displayed when the EIA 232 or Ethernet port has transmitted a...

Страница 25: ...epressing the MODE button changes the mode of the front panel displays to display the Previous Fault Log information PF Data Log mode the AC Power Interruption and Restoration Log Information AC Data...

Страница 26: ...utton will display the SSM switch programming Each channel with the SSM switch On will be denoted by a dark solid arrow and the Red Yellow Green and Walk indicators illuminated The CLEARANCE and DUAL...

Страница 27: ...hreshold Signal Inputs No Detect less than 15 Vrms Detect greater than 25 Vrms LEDguard High Threshold Signal Inputs No Detect less than 50 Vrms Detect greater than 70 Vrms Red Enable Input No Detect...

Страница 28: ...c Controller Voltage Monitor CVM No Fault less than 125 msec Fault greater than 175 msec Typical 150 msec 24Vdc Monitor No Fault less than 125 msec Fault greater than 175 msec Typical 150 msec Clearan...

Страница 29: ...ses when fault occurs O C Output Relay 2 Closed FTR Drive Opens when fault occurs O D Channel 12 Green I E Channel 11 Green I F Channel 10 Green I G Channel 9 Green I H Channel 8 Green I J Channel 7 G...

Страница 30: ...Yellow I y Channel 2 Walk I z Channel 1 Walk I AA Spare 1 BB Reset I CC Cabinet Interlock A I DD Cabinet Interlock B O EE Channel 6 Walk I FF Channel 4 Walk I GG Spare 2 HH Spare 3 8 1 2 SSM 12LE CONN...

Страница 31: ...ate with a MS 3116 22 55 SY 8 2 1 SSM 6LE CONNECTOR MS A PIN TERMINATIONS Pin Function I O A AC Line I I B AC Line II I C Output Relay 1 Open Stop Time Closes when fault occurs O D Output Relay 2 Clos...

Страница 32: ...II I m Controller Voltage Monitor I n 24V Monitor Inhibit I p Cabinet Interlock A q Spare 1 r Output Relay 1 Closed Stop Time Opens when fault occurs O s Start Delay Relay Closed Opens during Start D...

Страница 33: ...Monitor DB 9 RX pin 2 connect to TX pin 2 TX pin 3 connect to RX pin 3 DTR pin 4 connect to DTR pin 4 optional GND pin 5 connect to GND pin 5 A typical cable assembly for a DB 25 connector on the PC...

Отзывы: