EDI SSM-12LE Скачать руководство пользователя страница 26

SSM-LE Series 

Operations Manual 

Eberle Design Inc. 

Page 21 

recent fault event logged. Previous Failure #25 is the oldest fault event logged. If the 
display indicates PF 0, the Previous Failure event log is empty. 

6.5.2 AC DATA LOG DISPLAY MODE (AC DATA LOG) 

The second closure of the MODE button advances the display mode to the AC Data Log 
mode. The RESET button may be used to return to the normal operation display format. In 
this mode each closure of the INC button will advance the Fault Status display to the next 
AC Data Log event information. A total of 40 power interruptions and restorations labeled 
"AC 1" to "AC 40" can be reviewed. The display will sequence the log event type (AC) 
followed by the event number (1:40) followed by On or Off followed by the time and date of 
the event. If the display indicates AC 0, the AC Data Log is empty. 

6.5.3 CONFIGURATION DISPLAY MODE 

The third closure of the MODE button advances the display mode to the Configuration 
display mode. The RESET button may be used to return to the normal operation display 
format. The PROGRAM CARD indicator will be illuminated.  The Field Status display will 
present the compatible channel programming for each channel in a sequential fashion for 
each closure of the INC button. The Primary channel is indicated by the 

▼ symbol on the 

Channel Status display. All Secondary channels programmed permissive (jumper installed) 
with the displayed primary channel will be indicated on the Channel Status display with 

their 

 and 

 and 

 icons illuminated. Pressing the NEXT button will increment the 

display to the next Primary channel. 

These settings are read-only and require the Program Card jumpers to be changed. 

After all channel permissives are displayed, the next closure of the INC button will display 
the SSM switch programming. Each channel with the SSM switch On will be denoted by a 
dark solid arrow (

δ

) and the Red, Yellow, Green, and Walk indicators illuminated. The 

CLEARANCE and DUAL INDICATION indicators will be illuminated. If all SSM switches are 
in the Off position or the Red Enable input is not active, the Fault Status display will show 

A

OFF

@

, indicating that the Clearance and Dual Indication monitoring functions are 

disabled. Red Fail monitoring is also disabled by Red Enable input not active. 

6.5.4 CLOCK SET DISPLAY MODE 

The fourth closure of the MODE button advances the display mode to the Clock Set mode if 
the monitor is not currently in the fault mode. Each subsequent MODE button closure 
advances the Clock set display mode to the next field. The time and date fields are 
addressed in the following order: hours, minutes, month, date, year. The real time clock is 
set with the new time and date when the MODE button is pressed following the year entry. 
The RESET button may be used to return to the normal operation display format without 
modifying the time or date. 

6.6 CLEARING THE DATA LOGS 

Erasing the contents of the event  data logs  requires two deliberate steps to prevent 
inadvertent erasure of the logs. The first step is to depress and hold in both the MODE and 
INC buttons simultaneously followed by a momentary depression of the RESET button. The 
top LCD will flash the letters "CLr" to indicate it is in the clear data log mode and is waiting 
for the next step. Release the MODE and INC buttons. The final step to clear the data log is 
to depress and hold in the MODE button, then simultaneously depress the INC button and 
then release both buttons. The top LCD will return to alternately displaying the time and 
date. The RESET button can be depressed at any time to exit this mode without clearing 
the data log. The data log can also be cleared by using the CLEAR LOGS command in the 
EDI ECcom software. 

 

Содержание SSM-12LE

Страница 1: ...NS TECHNICAL INFORMATION FOR THE SSM 6LE SSM 6LEip SSM 6LEC SSM 12LE SSM 12LEip and SSM 12LEC SERIES SIGNAL MONITOR REVISION MARCH 2012 pn 888 1216 002 SSM LE Series NEMA TS 1 Enhanced Signal Monitor...

Страница 2: ...INFORMATION OF EBERLE DESIGN INC PUBLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING COPYRIGHT 2012 EDI MAINTENANCE NOTE THIS SIGNAL MONITOR UN...

Страница 3: ...tion 3 Enhanced Features 7 3 1 Hardware Features 7 3 2 Dual Indication Monitoring 7 3 2 1 GY ENABLE Option 8 3 2 2 Walk Disable Option 8 3 3 Minimum Yellow Clearance Monitoring 8 3 4 External Watchdog...

Страница 4: ...TX Indicator 19 6 1 14 PREV FAIL Indicator 19 6 2 Field Status Display 19 6 3 LED Status Display 19 6 3 1 POWER Indicator 19 6 3 2 FAULT Indicator 20 6 3 3 DIAGNOSTIC Indicator 20 6 4 Buttons 20 6 4 1...

Страница 5: ...8 3 EIA 232 Connector 27 8 3 1 EIA 232 Cable to a PC 28 8 4 Ethernet LAN Port 28 8 4 1 Ethernet LAN Cable 28...

Страница 6: ...RE OVERVIEW 1 2 1 LIQUID CRYSTAL STATUS AND FIELD DISPLAY The SSM LE Series uses a Liquid Crystal Display LCD to show monitor status and two icon based LCDs to show field signal channel and fault stat...

Страница 7: ...g either full wave or positive and negative half wave sinusoidal field signal inputs at the specified voltage levels When triggered by the detection of a fault condition which exists longer than the m...

Страница 8: ...reshold value to determine On Off status This differs from conventional standard NEMA operation where the active threshold is picked according to the color of the field signal Once the high and low On...

Страница 9: ...ill be disabled when the RED ENABLE input is not active 2 2 1 RED ENABLE INPUT The RED ENABLE input will be sensed as active by the SSM LE Series when it exceeds the Red Enable Input threshold Section...

Страница 10: ...lt mode transfer the OUTPUT relay contacts to the Fault position and display the CVM status screen When the TRUE low state is absent for less than the CVM No Fault time the SSM LE Series will not tran...

Страница 11: ...and the last component to sense a proper AC LINE operating voltage The AC LINE and AC NEUTRAL inputs are used to generate the internal voltage supplies required to operate the monitor AC NEUTRAL also...

Страница 12: ...ruption The correct fault indications will be displayed upon restoration of AC Line power This EEPROM device requires no battery back up The time of day in the SSM LE Series is stored in a battery bac...

Страница 13: ...he Clearance Fail Fault time 7 4 The Yellow Change interval consists of the duration of time in which the Yellow field signal input is active in a sequence from Green to Yellow to Red When this minimu...

Страница 14: ...A real time clock is provided on the SSM LE series Signal Monitor to identify each event occurrence with the time of day and date This information is displayed and stored along with the event status w...

Страница 15: ...eries will enter the fault mode transfer the Output relay contacts to the Fault position and display the appropriate CONFLICT DUAL INDICATION or RED FAIL status screen along with RP STATUS The unit wi...

Страница 16: ...FYA Overlap phase must be driven by a load switch monitored on channels 9 10 11 12 respectively The SSM LE Series associates channel 1 with 9 channel 3 with 10 channel 5 with 11 and channel 7 with 12...

Страница 17: ...proaches This mode requires that the Controller Unit be capable of remapping the Protected Green Arrow signal driver to the channel 9 10 11 and 12 Yellow load switch inputs The cabinet must be re wire...

Страница 18: ...from the flashing Yellow Arrow 1 3 5 7 to the solid Red Arrow 1 3 5 7 without a minimum clearance time on the solid Yellow Arrow 1 3 5 7 The fault icon will be displayed for the FYAc channel 1 3 5 7 i...

Страница 19: ...vent 4 1 2 CURRENT STATUS S Fault Type the fault type description Field Status the current or latched RYGW field status and RMS voltages Cabinet Temperature the current or latched temperature if the m...

Страница 20: ...the reported configuration 4 1 7 SIGNAL SEQUENCE EVENT LOG The Signal Sequence event log graphically displays all signal states and Red Enable state for up 30 seconds prior to the SSM LE Series fault...

Страница 21: ...fault mode until the Program Card is correctly seated and the SSM LE Series is reset by the RESET button or the EXTERNAL RESET input 5 2 MINIMUM FLASH TIME PROGRAMMING It is recommended that the Mini...

Страница 22: ...2 2 2 5 4 5 CONTROLLER VOLTAGE MONITOR CVM LATCH PROGRAMMING The CVM Latch function is ENABLED by setting the Option switch labeled CVM LATCH to the ON position See Section 2 3 2 1 5 4 6 24VDC MONITOR...

Страница 23: ...w all active field output signals at the time of the CVM fault 6 1 4 24V 1 INDICATOR The 24V 1 indicator will be illuminated when unit detects a 24V 1 fault The Field Status display will show all acti...

Страница 24: ...dicator will be displayed when the EIA 232 or Ethernet port has correctly received a message 6 1 13 TX INDICATOR The Tx indicator will be displayed when the EIA 232 or Ethernet port has transmitted a...

Страница 25: ...epressing the MODE button changes the mode of the front panel displays to display the Previous Fault Log information PF Data Log mode the AC Power Interruption and Restoration Log Information AC Data...

Страница 26: ...utton will display the SSM switch programming Each channel with the SSM switch On will be denoted by a dark solid arrow and the Red Yellow Green and Walk indicators illuminated The CLEARANCE and DUAL...

Страница 27: ...hreshold Signal Inputs No Detect less than 15 Vrms Detect greater than 25 Vrms LEDguard High Threshold Signal Inputs No Detect less than 50 Vrms Detect greater than 70 Vrms Red Enable Input No Detect...

Страница 28: ...c Controller Voltage Monitor CVM No Fault less than 125 msec Fault greater than 175 msec Typical 150 msec 24Vdc Monitor No Fault less than 125 msec Fault greater than 175 msec Typical 150 msec Clearan...

Страница 29: ...ses when fault occurs O C Output Relay 2 Closed FTR Drive Opens when fault occurs O D Channel 12 Green I E Channel 11 Green I F Channel 10 Green I G Channel 9 Green I H Channel 8 Green I J Channel 7 G...

Страница 30: ...Yellow I y Channel 2 Walk I z Channel 1 Walk I AA Spare 1 BB Reset I CC Cabinet Interlock A I DD Cabinet Interlock B O EE Channel 6 Walk I FF Channel 4 Walk I GG Spare 2 HH Spare 3 8 1 2 SSM 12LE CONN...

Страница 31: ...ate with a MS 3116 22 55 SY 8 2 1 SSM 6LE CONNECTOR MS A PIN TERMINATIONS Pin Function I O A AC Line I I B AC Line II I C Output Relay 1 Open Stop Time Closes when fault occurs O D Output Relay 2 Clos...

Страница 32: ...II I m Controller Voltage Monitor I n 24V Monitor Inhibit I p Cabinet Interlock A q Spare 1 r Output Relay 1 Closed Stop Time Opens when fault occurs O s Start Delay Relay Closed Opens during Start D...

Страница 33: ...Monitor DB 9 RX pin 2 connect to TX pin 2 TX pin 3 connect to RX pin 3 DTR pin 4 connect to DTR pin 4 optional GND pin 5 connect to GND pin 5 A typical cable assembly for a DB 25 connector on the PC...

Отзывы: