SSM-LE Series 

Operations Manual 

Eberle Design Inc. 

Page 5 

A voltage greater than the +24V Monitor input threshold (Section 7.1.4) applied to both of 
the +24V MONITOR inputs will be sensed by the SSM-LE Series

 

as adequate for operation 

of the cabinet assembly. A voltage less than the +24V Monitor input threshold applied to 
either of the +24V MONITOR inputs will be sensed as inadequate for proper operation. 
When a +24V MONITOR input is sensed as inadequate for more than the +24V Monitor 
Fault time (7.4), the SSM-LE Series

 

will enter the fault mode and transfer the  OUTPUT 

relay contacts to the Fault position. When a +24V MONITOR input is sensed as inadequate 
for less than the +24V Monitor No-Fault time, the SSM-LE Series

 

will not transfer the 

OUTPUT relay contacts to the Fault position. A +24Vdc failure during the programmed 
Minimum Flash time or during a Power Failure will not cause a fault condition.  

2.3.1.1 +24VDC MONITOR INHIBIT INPUT  

A +24V MONITOR INHIBIT input is provided to inhibit the operation of the +24Vdc Monitor. 
Application of a logic TRUE (low) state to this input will disable the operation of the +24Vdc 
Monitor. 

2.3.1.2 +24VDC MONITOR LATCH INPUT  

An Option Switch is supplied on the front panel to allow +24Vdc failures to latch in the fault 
condition until the unit is reset by the activation of the RESET button or the EXTERNAL 
RESET input. See Section 5.4.5. A +24Vdc failure during the programmed Minimum Flash 
time or during a Power Failure will not cause a latched fault condition.  

2.3.2 CONTROLLER VOLTAGE / FAULT MONITOR INPUT  

This input is to be connected to the CONTROLLER UNIT VOLTAGE MONITOR (CVM) 
output from the Controller Unit. When the TRUE (low) state is absent for more than the 
CVM Fault time (7.4), the SSM-LE Series

 

will enter the fault mode, transfer the OUTPUT 

relay contacts to the Fault position, and display the CVM status screen. When the TRUE 
(low) state is absent for less than  the CVM  No-Fault time, the SSM-LE Series

 

will not 

transfer the OUTPUT relay contacts to the Fault position. The SSM-LE Series

 

will 

automatically reset the OUTPUT relay when the True (low) state is restored to the input. 
The  SSM-LE Series

 

will remain in the fault mode for at  least the time determined by the 

Minimum Flash programming. A CVM failure during the programmed Minimum Flash time 
or during a Power Failure will not cause a fault condition.  

2.3.2.1 CVM MONITOR LATCH INPUT  

An Option Switch  is supplied on the front panel  to allow CVM failures to latch in the fault 
condition until the unit is reset by the activation of the RESET button or the EXTERNAL 
RESET input. See Section 5.4.5. A CVM failure during the programmed Minimum Flash 
time or during a Power Failure will not cause a latched fault condition. 

2.3.2.2 CVM LOG DISABLE   

If CVM events are not related to a malfunction condition and occur on a regular basis such 
as Time of Day flash, the logging of these events can be disabled. See Section 5.4.7.  

2.4 POWER FAILURE DETECTION  

When the AC LINE voltage is below the minimum AC Line drop-out level (Section 7.1.2) for 
the Power Fail Respond time  (7.4),  the  SSM-LE Series

 

will suspend all fault monitoring 

functions, de-energize the OUTPUT relay, and de-energize the START relay. The POWER 
indicator on the front panel will flash at a rate of 2Hz to indicate the low voltage status. 

When the AC LINE voltage returns above the maximum AC Line restore level (Section 
7.1.2) for the Power Fail Restore time (7.4), the monitor will resume normal operation and 
the POWER indicator on the front panel will remain illuminated. After a 2.5  +

_0.5 second 

delay the START relay will be energized. After a programmable delay determined by the 
Minimum Flash programming (see Section 5.2), the OUTPUT relay will be energized. 

Содержание SSM-12LE

Страница 1: ...NS TECHNICAL INFORMATION FOR THE SSM 6LE SSM 6LEip SSM 6LEC SSM 12LE SSM 12LEip and SSM 12LEC SERIES SIGNAL MONITOR REVISION MARCH 2012 pn 888 1216 002 SSM LE Series NEMA TS 1 Enhanced Signal Monitor...

Страница 2: ...INFORMATION OF EBERLE DESIGN INC PUBLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING COPYRIGHT 2012 EDI MAINTENANCE NOTE THIS SIGNAL MONITOR UN...

Страница 3: ...tion 3 Enhanced Features 7 3 1 Hardware Features 7 3 2 Dual Indication Monitoring 7 3 2 1 GY ENABLE Option 8 3 2 2 Walk Disable Option 8 3 3 Minimum Yellow Clearance Monitoring 8 3 4 External Watchdog...

Страница 4: ...TX Indicator 19 6 1 14 PREV FAIL Indicator 19 6 2 Field Status Display 19 6 3 LED Status Display 19 6 3 1 POWER Indicator 19 6 3 2 FAULT Indicator 20 6 3 3 DIAGNOSTIC Indicator 20 6 4 Buttons 20 6 4 1...

Страница 5: ...8 3 EIA 232 Connector 27 8 3 1 EIA 232 Cable to a PC 28 8 4 Ethernet LAN Port 28 8 4 1 Ethernet LAN Cable 28...

Страница 6: ...RE OVERVIEW 1 2 1 LIQUID CRYSTAL STATUS AND FIELD DISPLAY The SSM LE Series uses a Liquid Crystal Display LCD to show monitor status and two icon based LCDs to show field signal channel and fault stat...

Страница 7: ...g either full wave or positive and negative half wave sinusoidal field signal inputs at the specified voltage levels When triggered by the detection of a fault condition which exists longer than the m...

Страница 8: ...reshold value to determine On Off status This differs from conventional standard NEMA operation where the active threshold is picked according to the color of the field signal Once the high and low On...

Страница 9: ...ill be disabled when the RED ENABLE input is not active 2 2 1 RED ENABLE INPUT The RED ENABLE input will be sensed as active by the SSM LE Series when it exceeds the Red Enable Input threshold Section...

Страница 10: ...lt mode transfer the OUTPUT relay contacts to the Fault position and display the CVM status screen When the TRUE low state is absent for less than the CVM No Fault time the SSM LE Series will not tran...

Страница 11: ...and the last component to sense a proper AC LINE operating voltage The AC LINE and AC NEUTRAL inputs are used to generate the internal voltage supplies required to operate the monitor AC NEUTRAL also...

Страница 12: ...ruption The correct fault indications will be displayed upon restoration of AC Line power This EEPROM device requires no battery back up The time of day in the SSM LE Series is stored in a battery bac...

Страница 13: ...he Clearance Fail Fault time 7 4 The Yellow Change interval consists of the duration of time in which the Yellow field signal input is active in a sequence from Green to Yellow to Red When this minimu...

Страница 14: ...A real time clock is provided on the SSM LE series Signal Monitor to identify each event occurrence with the time of day and date This information is displayed and stored along with the event status w...

Страница 15: ...eries will enter the fault mode transfer the Output relay contacts to the Fault position and display the appropriate CONFLICT DUAL INDICATION or RED FAIL status screen along with RP STATUS The unit wi...

Страница 16: ...FYA Overlap phase must be driven by a load switch monitored on channels 9 10 11 12 respectively The SSM LE Series associates channel 1 with 9 channel 3 with 10 channel 5 with 11 and channel 7 with 12...

Страница 17: ...proaches This mode requires that the Controller Unit be capable of remapping the Protected Green Arrow signal driver to the channel 9 10 11 and 12 Yellow load switch inputs The cabinet must be re wire...

Страница 18: ...from the flashing Yellow Arrow 1 3 5 7 to the solid Red Arrow 1 3 5 7 without a minimum clearance time on the solid Yellow Arrow 1 3 5 7 The fault icon will be displayed for the FYAc channel 1 3 5 7 i...

Страница 19: ...vent 4 1 2 CURRENT STATUS S Fault Type the fault type description Field Status the current or latched RYGW field status and RMS voltages Cabinet Temperature the current or latched temperature if the m...

Страница 20: ...the reported configuration 4 1 7 SIGNAL SEQUENCE EVENT LOG The Signal Sequence event log graphically displays all signal states and Red Enable state for up 30 seconds prior to the SSM LE Series fault...

Страница 21: ...fault mode until the Program Card is correctly seated and the SSM LE Series is reset by the RESET button or the EXTERNAL RESET input 5 2 MINIMUM FLASH TIME PROGRAMMING It is recommended that the Mini...

Страница 22: ...2 2 2 5 4 5 CONTROLLER VOLTAGE MONITOR CVM LATCH PROGRAMMING The CVM Latch function is ENABLED by setting the Option switch labeled CVM LATCH to the ON position See Section 2 3 2 1 5 4 6 24VDC MONITOR...

Страница 23: ...w all active field output signals at the time of the CVM fault 6 1 4 24V 1 INDICATOR The 24V 1 indicator will be illuminated when unit detects a 24V 1 fault The Field Status display will show all acti...

Страница 24: ...dicator will be displayed when the EIA 232 or Ethernet port has correctly received a message 6 1 13 TX INDICATOR The Tx indicator will be displayed when the EIA 232 or Ethernet port has transmitted a...

Страница 25: ...epressing the MODE button changes the mode of the front panel displays to display the Previous Fault Log information PF Data Log mode the AC Power Interruption and Restoration Log Information AC Data...

Страница 26: ...utton will display the SSM switch programming Each channel with the SSM switch On will be denoted by a dark solid arrow and the Red Yellow Green and Walk indicators illuminated The CLEARANCE and DUAL...

Страница 27: ...hreshold Signal Inputs No Detect less than 15 Vrms Detect greater than 25 Vrms LEDguard High Threshold Signal Inputs No Detect less than 50 Vrms Detect greater than 70 Vrms Red Enable Input No Detect...

Страница 28: ...c Controller Voltage Monitor CVM No Fault less than 125 msec Fault greater than 175 msec Typical 150 msec 24Vdc Monitor No Fault less than 125 msec Fault greater than 175 msec Typical 150 msec Clearan...

Страница 29: ...ses when fault occurs O C Output Relay 2 Closed FTR Drive Opens when fault occurs O D Channel 12 Green I E Channel 11 Green I F Channel 10 Green I G Channel 9 Green I H Channel 8 Green I J Channel 7 G...

Страница 30: ...Yellow I y Channel 2 Walk I z Channel 1 Walk I AA Spare 1 BB Reset I CC Cabinet Interlock A I DD Cabinet Interlock B O EE Channel 6 Walk I FF Channel 4 Walk I GG Spare 2 HH Spare 3 8 1 2 SSM 12LE CONN...

Страница 31: ...ate with a MS 3116 22 55 SY 8 2 1 SSM 6LE CONNECTOR MS A PIN TERMINATIONS Pin Function I O A AC Line I I B AC Line II I C Output Relay 1 Open Stop Time Closes when fault occurs O D Output Relay 2 Clos...

Страница 32: ...II I m Controller Voltage Monitor I n 24V Monitor Inhibit I p Cabinet Interlock A q Spare 1 r Output Relay 1 Closed Stop Time Opens when fault occurs O s Start Delay Relay Closed Opens during Start D...

Страница 33: ...Monitor DB 9 RX pin 2 connect to TX pin 2 TX pin 3 connect to RX pin 3 DTR pin 4 connect to DTR pin 4 optional GND pin 5 connect to GND pin 5 A typical cable assembly for a DB 25 connector on the PC...

Отзывы: