EDI SSM-12LE Скачать руководство пользователя страница 16

SSM-LE Series 

Operations Manual 

Eberle Design Inc. 

Page 11 

- WARNING - 

EDI does not provide any guidelines, warrants, or recommendations for the use of 
protected/permissive left-turn phasing. The underlying assumption is that the traffic 
engineer has decided that this form of protected/permissive control is the most 
appropriate left-turn treatment, and all necessary considerations have been made. 
Until official rulemaking action by the MUTCD has occurred, the operation and 
functional parameters of the SSM-LE Series

 

FYA and FYAc modes are subject to 

change.

 

Two cabinet configurations are supported depending on the number of load switches 
provided and the capabilities of the Controller Unit.  A  Flashing Yellow Arrow approach is 
actually monitored using two physical  channels of the SSM-LE  Series.  In the basic  FYA 
mode  of the unit, one additional load switch is required for each FYA approach to be 
monitored. Thus a cabinet providing four vehicle phases, four pedestrian phases, and four 
FYA approaches would require sixteen load switches.  

The compact FYAc mode  requires the Controller Unit to  remap  the Yellow outputs of the 
pedestrian load switches  to drive the protected Green Arrow signals  of the FYA 
approaches. In this mode the cabinet can provide the four FYA approaches with an existing 
twelve position back panel. Configuration settings are described in Section 5.4.8. 

3.11.1 BASIC FYA MODE 

The cabinet must be wired such that for each FYA approach, the solid Green protected 
Arrow is driven by a load switch monitored on channels 1, 3, 5, and 7. The associated solid 
Red  Arrow, solid Yellow Arrow, and flashing Yellow Arrow  (FYA  Overlap phase) must be 
driven by a load switch monitored on channels  9, 10, 11, 12  respectively. The SSM-LE 
Series  associates channel 1 with  9, channel 3 with 10, channel 5 with 11, and channel 7 
with 12 when FYA monitoring is enabled for that respective approach. 

If a channel pair is enabled for FYA operation, the SSM-LE Series  will  monitor the FYA 
logical channel pair for the following fault conditions: 

a. 

Conflict 

i.  Channel conflicts are detected based on the Permissive programming 

jumpers on the Program Card for each channel. This operation 
remains unchanged from normal Nema operation. 

b. 

Red Fail 

i.  A Red Fail fault will occur if the solid Red Arrow  AND solid Yellow 

Arrow  AND flashing Yellow Arrow  AND solid Green Arrow  all remain 
inactive for the Red Fail fault response time. The fault icon (

) will be 

displayed for both channels of the pair. The Red and Yellow inputs for 
channels 1, 3, 5, 7  do not affect the Red Fail condition for the FYA 
channels 9, 10, 11, 12. 

c. 

Dual Indication 

i.  A Dual Indication fault will occur if any two or more of the solid Red 

Arrow, solid Yellow Arrow, flashing Yellow Arrow, or solid Green Arrow 
signal combinations are active simultaneously for the Dual Indication 
fault response time. The fault icon (

) will be displayed for the FYA 

channel 9, 10, 11, 12. The fault icon (

) will also be displayed for the 

solid Green Arrow  channel 1, 3, 5, 7 IF the solid Green Arrow  was 
active. 

ii.  If the Dual Indication function  (SSM)  is enabled  for the solid Green 

Arrow channels (1, 3, 5, 7) then a Dual Indication fault will occur if any 
two or more of the Red, Yellow, or solid Green Arrow inputs (1, 3, 5, 7) 
are active simultaneously for the Dual Indication fault response time. 

d. 

Clearance 

i.  A Clearance fault will be detected if the channel  pair  sequences from 

the solid Green Arrow (1, 3, 5, 7) to the solid Red Arrow (9, 10, 11, 12) 

Содержание SSM-12LE

Страница 1: ...NS TECHNICAL INFORMATION FOR THE SSM 6LE SSM 6LEip SSM 6LEC SSM 12LE SSM 12LEip and SSM 12LEC SERIES SIGNAL MONITOR REVISION MARCH 2012 pn 888 1216 002 SSM LE Series NEMA TS 1 Enhanced Signal Monitor...

Страница 2: ...INFORMATION OF EBERLE DESIGN INC PUBLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING COPYRIGHT 2012 EDI MAINTENANCE NOTE THIS SIGNAL MONITOR UN...

Страница 3: ...tion 3 Enhanced Features 7 3 1 Hardware Features 7 3 2 Dual Indication Monitoring 7 3 2 1 GY ENABLE Option 8 3 2 2 Walk Disable Option 8 3 3 Minimum Yellow Clearance Monitoring 8 3 4 External Watchdog...

Страница 4: ...TX Indicator 19 6 1 14 PREV FAIL Indicator 19 6 2 Field Status Display 19 6 3 LED Status Display 19 6 3 1 POWER Indicator 19 6 3 2 FAULT Indicator 20 6 3 3 DIAGNOSTIC Indicator 20 6 4 Buttons 20 6 4 1...

Страница 5: ...8 3 EIA 232 Connector 27 8 3 1 EIA 232 Cable to a PC 28 8 4 Ethernet LAN Port 28 8 4 1 Ethernet LAN Cable 28...

Страница 6: ...RE OVERVIEW 1 2 1 LIQUID CRYSTAL STATUS AND FIELD DISPLAY The SSM LE Series uses a Liquid Crystal Display LCD to show monitor status and two icon based LCDs to show field signal channel and fault stat...

Страница 7: ...g either full wave or positive and negative half wave sinusoidal field signal inputs at the specified voltage levels When triggered by the detection of a fault condition which exists longer than the m...

Страница 8: ...reshold value to determine On Off status This differs from conventional standard NEMA operation where the active threshold is picked according to the color of the field signal Once the high and low On...

Страница 9: ...ill be disabled when the RED ENABLE input is not active 2 2 1 RED ENABLE INPUT The RED ENABLE input will be sensed as active by the SSM LE Series when it exceeds the Red Enable Input threshold Section...

Страница 10: ...lt mode transfer the OUTPUT relay contacts to the Fault position and display the CVM status screen When the TRUE low state is absent for less than the CVM No Fault time the SSM LE Series will not tran...

Страница 11: ...and the last component to sense a proper AC LINE operating voltage The AC LINE and AC NEUTRAL inputs are used to generate the internal voltage supplies required to operate the monitor AC NEUTRAL also...

Страница 12: ...ruption The correct fault indications will be displayed upon restoration of AC Line power This EEPROM device requires no battery back up The time of day in the SSM LE Series is stored in a battery bac...

Страница 13: ...he Clearance Fail Fault time 7 4 The Yellow Change interval consists of the duration of time in which the Yellow field signal input is active in a sequence from Green to Yellow to Red When this minimu...

Страница 14: ...A real time clock is provided on the SSM LE series Signal Monitor to identify each event occurrence with the time of day and date This information is displayed and stored along with the event status w...

Страница 15: ...eries will enter the fault mode transfer the Output relay contacts to the Fault position and display the appropriate CONFLICT DUAL INDICATION or RED FAIL status screen along with RP STATUS The unit wi...

Страница 16: ...FYA Overlap phase must be driven by a load switch monitored on channels 9 10 11 12 respectively The SSM LE Series associates channel 1 with 9 channel 3 with 10 channel 5 with 11 and channel 7 with 12...

Страница 17: ...proaches This mode requires that the Controller Unit be capable of remapping the Protected Green Arrow signal driver to the channel 9 10 11 and 12 Yellow load switch inputs The cabinet must be re wire...

Страница 18: ...from the flashing Yellow Arrow 1 3 5 7 to the solid Red Arrow 1 3 5 7 without a minimum clearance time on the solid Yellow Arrow 1 3 5 7 The fault icon will be displayed for the FYAc channel 1 3 5 7 i...

Страница 19: ...vent 4 1 2 CURRENT STATUS S Fault Type the fault type description Field Status the current or latched RYGW field status and RMS voltages Cabinet Temperature the current or latched temperature if the m...

Страница 20: ...the reported configuration 4 1 7 SIGNAL SEQUENCE EVENT LOG The Signal Sequence event log graphically displays all signal states and Red Enable state for up 30 seconds prior to the SSM LE Series fault...

Страница 21: ...fault mode until the Program Card is correctly seated and the SSM LE Series is reset by the RESET button or the EXTERNAL RESET input 5 2 MINIMUM FLASH TIME PROGRAMMING It is recommended that the Mini...

Страница 22: ...2 2 2 5 4 5 CONTROLLER VOLTAGE MONITOR CVM LATCH PROGRAMMING The CVM Latch function is ENABLED by setting the Option switch labeled CVM LATCH to the ON position See Section 2 3 2 1 5 4 6 24VDC MONITOR...

Страница 23: ...w all active field output signals at the time of the CVM fault 6 1 4 24V 1 INDICATOR The 24V 1 indicator will be illuminated when unit detects a 24V 1 fault The Field Status display will show all acti...

Страница 24: ...dicator will be displayed when the EIA 232 or Ethernet port has correctly received a message 6 1 13 TX INDICATOR The Tx indicator will be displayed when the EIA 232 or Ethernet port has transmitted a...

Страница 25: ...epressing the MODE button changes the mode of the front panel displays to display the Previous Fault Log information PF Data Log mode the AC Power Interruption and Restoration Log Information AC Data...

Страница 26: ...utton will display the SSM switch programming Each channel with the SSM switch On will be denoted by a dark solid arrow and the Red Yellow Green and Walk indicators illuminated The CLEARANCE and DUAL...

Страница 27: ...hreshold Signal Inputs No Detect less than 15 Vrms Detect greater than 25 Vrms LEDguard High Threshold Signal Inputs No Detect less than 50 Vrms Detect greater than 70 Vrms Red Enable Input No Detect...

Страница 28: ...c Controller Voltage Monitor CVM No Fault less than 125 msec Fault greater than 175 msec Typical 150 msec 24Vdc Monitor No Fault less than 125 msec Fault greater than 175 msec Typical 150 msec Clearan...

Страница 29: ...ses when fault occurs O C Output Relay 2 Closed FTR Drive Opens when fault occurs O D Channel 12 Green I E Channel 11 Green I F Channel 10 Green I G Channel 9 Green I H Channel 8 Green I J Channel 7 G...

Страница 30: ...Yellow I y Channel 2 Walk I z Channel 1 Walk I AA Spare 1 BB Reset I CC Cabinet Interlock A I DD Cabinet Interlock B O EE Channel 6 Walk I FF Channel 4 Walk I GG Spare 2 HH Spare 3 8 1 2 SSM 12LE CONN...

Страница 31: ...ate with a MS 3116 22 55 SY 8 2 1 SSM 6LE CONNECTOR MS A PIN TERMINATIONS Pin Function I O A AC Line I I B AC Line II I C Output Relay 1 Open Stop Time Closes when fault occurs O D Output Relay 2 Clos...

Страница 32: ...II I m Controller Voltage Monitor I n 24V Monitor Inhibit I p Cabinet Interlock A q Spare 1 r Output Relay 1 Closed Stop Time Opens when fault occurs O s Start Delay Relay Closed Opens during Start D...

Страница 33: ...Monitor DB 9 RX pin 2 connect to TX pin 2 TX pin 3 connect to RX pin 3 DTR pin 4 connect to DTR pin 4 optional GND pin 5 connect to GND pin 5 A typical cable assembly for a DB 25 connector on the PC...

Отзывы: