pag.18
EN
420010243004 MULTICALOR 170.1-200.1 PR/PR
ELECTRICAL CONNECTIONS
All burners are factory tested and set at 400 V 50 Hz three-phase for motors and 230 V 50 Hz monophase with neutral
for auxiliaries. If it is necessary to supply the burner at 230 V 50 Hz without neutral,make the necessary alterations
referring to the wiring diagram of the burner and check that the termal relay is within the absorption range of the
motor. Also check that the fan motor rotates in the correct direction.
CONNECTION TO THE GAS PIPELINE
Once connected the burner to the gas pipeline, it is necessary to control that this last is perfectly sealed. Also verify that
the chimney is not obstructed. Open the gas cock and carefully bleed the piping through the pressure gauge connector,
then check the pressure value trough a suitable gauge. Power on the system and adjust the thermostats to the desired
temperature. When thermostats close, the sealing control device runs a seal test of valves; at the end of the test the bur-
ner will be enabled to run the start-up sequence.
M
Air
Gas
313
160
170
141
120
150
314
349
151
155
100
143
107
To be supplied by the installer
To be supplied by the installer
100 Burner
107 Pilot gas filter/governor
120 Air
damper
141 Ball
valve
142 Gas
filter
143 Antivibration
coupling
144 Gas
governor
150 Batterfly
valve
151 Gas train Dungs MB-DLE....
155 Pilot gas train
160
Kit
tightness control (optional)
170
Kit
tightness control for pilot gas valve (optional)
313 Min.gas pressure switch
314 Max.gas pressure switch (optional)
349 Air/gas damper motor
CONNECTION DIAGRAM FOR BURNERS WITH SEPARATE PILOT
(GAS TRAIN DUNGS MB-DLE...)
CONNECTION DIAGRAM FOR BURNERS WITH SEPARATE PILOT
(gas train Dungs MB-DLE...)
100
Burner
107
Pilot gas filter/governor
120
Air damper
141
Ball valve
142
Gas filter
143
Antivibration coupling
144
Gas governor
150
Batterfly valve
151
Gas train Dungs MB-DLE....
155
Pilot gas train
160
Kit tightness control (optional)
170
Kit tightness control for pilot gas valve (optional)
313
Min.gas pressure switch
314
Max.gas pressure switch (optional)
349
Air/gas damper motor
M
Air
Gas
313
160
170
142
141
120
150
314
349
151
155
100
143
To be supplied by the installer
To be supplied by the installer
144
CONNECTION DIAGRAM FOR BURNERS WITH SEPARATE PILOT
(GAS TRAIN KROMSCHRODER VCS...)
107
100 Burner
107 Pilot gas filter/governor
120 Air
damper
141 Ball
valve
142 Gas
filter
143 Antivibration
coupling
144 Gas
governor
150 Batterfly
valve
151 Gas
train
Kromschroder VCS
....
155 Pilot gas train
160
Kit
tightness control (optional)
170
Kit
tightness control for pilot gas valve (optional)
313 Min
.
gas pressure switch
314 Max
.
gas pressure switch (optional)
349 Air/gas damper motor
CONNECTION DIAGRAM FOR BURNERS WITH SEPARATE PILOT
(gas train Kromschroder VCS...)
100
Burner
107
Pilot gas filter/governor
120
Air damper
141
Ball valve
142
Gas filter
143
Antivibration coupling
144
Gas governor
150
Batterfly valve
151
Gas train Kromschroder VCS....
155
Pilot gas train
160
Kit tightness control (optional)
170
Kit tightness control for pilot gas valve (optional)
313
Min.gas pressure switch
314
Max.gas pressure switch (optional)
349
Air/gas damper motor