26

CONEXIONES ELÉCTRICAS

Cuadro de conexionado - Calibres recomendados de cables y fusibles para 115 y 230 Voltaje

 

POTENCIA 

  

CORRIENTE

 

CALIBRE

 

         

                   DISTANCIA EN PIES DEL MOTOR A LA ALIMENTACIÓN ELÉCTRICA 

 

DEL  

DE PLENA  

FUSIBLE/

   

CALIBRE CABLES

 

0-100   

101-200   

201-300   

301-400   

401-500 

  MOTOR HP   VOLTAJE    CARGA (A) 

  

INTERRUPTOR

   

 MÍN., AWG (mm2)

 

 

 CALIBRE CABLES, AWG (mm

2

 

115/230  16.32/8.16 

30/15 

10/14 (5.5/2) 

10/14 (5.5/2) 

8/14 (2/2) 

6/14 (14/2) 

6/12 (14/3)  4/10 (21/5.5) 

 

 

1-1/2 

115/230  20.09/10.05 

30/15 

10/14 (5.5/2) 

10/14 (5.5/2)  8/14 (8.4/2) 

6/12 (14/3)  4/10 (21/5.5)  4/10 (21/5.5) 

 

 

115/230  20.75/10.38 

30/20 

8/12 (8.9/3) 

8/12 (8.9/3) 

8/12 (8.4/3)   6/10 (14/5.5)  4/10 (21/5.5)  4/10 (21/5.5) 

Para obtener repuestos o asistencia, llame a ECO-FLO Servicio al Cliente al 1-877 326-3561

Desconecte la energía antes de trabajar en la 

bomba, motor, interruptor de presión o cableado.

El motor puede estar caliente.  

Espere 20 minutos a que se enfríe.

Puede haber presión de agua en la 

bomba, tuberías y/o tanque. Drene 

el agua para aliviar la presión.

Configuración de voltaje del motor

Los motores están diseñados para funcionar con corriente 

de 115 o 230 voltios. Asegúrese de que el voltaje del  

motor sea igual que el del suministro de energía.

Para ajustar el motor a la tensión correcta, primero quite 

la placa de la cubierta trasera. Siguiente diapositiva la 

conversión de tensión cambia a la tensión correcta. EL 

CABLEADO DE LA BOMBA PARA EL

VOLTAJE INCORRECTO  

PROVOCARÁ DAÑOS EN 

LA BOMBA.

 

Plate Screws

Motor Cover Plate

4.  Utilice calibres de cables según las especificaciones  

  del Cuadro de Cableado. De ser posible, conecte    

  la bomba a un circuito de derivación separado al que  

  no estén conectados otros aparatos. 

5.  No haga la conexión a tierra a una línea de gas.

6.  Conecte los cables en el motor según el diagrama de  

  la placa informativa. Si el diagrama de la placa infor-  

  mativa difiere del diagrama anterior, siga el diagrama  

  de la placa.

7.  Si este procedimiento o los diagramas de cableado   

  resultan confusos, consulte con un electricista  

 

  calificado.

AVISO

 

La bomba debe estar en un circuito dedicado, 

no compartido con otro equipo.

Conexiones de cableado

   

                  Riesgo de descarga eléctrica. La 

electricidad puede causar un choque eléctrico, quemar o 

matar.

1.  Para evitar descargas eléctricas peligrosas o fatales,  

  apague el motor antes de trabajar en las conexiones  

 eléctricas.

2.  Conecte el motor a tierra, antes de conectar la fuente  

  de energía eléctrica. Si no se hace la conexión a tierra  

  del motor se puede generar una descarga eléctrica    

  peligrosa o fatal.

3.  El voltaje de suministro debe estar dentro del +/- 10%  

  del voltaje que aparece en la placa informativa. El    

  voltaje incorrecto puede causar un incendio o dañar el  

  motor y anula la garantía. En caso de duda, consulte  

  con un electricista.

ADVERTENCIA

PRECAUCIÓN
PRECAUCIÓN

Tornillos de la  

placa

Placa de cubierta del motor

VIVO
TO BREAKER

VIVO
TO BREAKER

VIVO
TO BREAKER

230

115

NEUTRO
TO BREAKER

115V

230V

L1

L2

L1

L2

Содержание EFLS10

Страница 1: ...Owner s Manual Cast Iron Sprinkler Pumps General Safety 2 Installation 3 5 Electrical 6 Operation 7 Troubleshooting 8 Repair Parts 9 Warranty 10 TABLE OF CONTENTS...

Страница 2: ...in water and are wearing insulted protective shoes under flood conditions Contact your local electric company or a qualified licensed electrician for dicconnecting electrical service prior to pump rem...

Страница 3: ...normally operates at high temperature and will be too hot to touch It is protected from heat dam age during operation by an automatic internal cutoff switch Before handling pump or motor stop motor an...

Страница 4: ...toward pump Surface Water Applications Figure 3A and 3B A Vertical from Surface Water to Pump 1 Foot Valve with Strainer attached to PVC pipe 2 Install check valve in horizontal pipe B Horizontal fro...

Страница 5: ...able to pull water from the well 1 Bolt pump to solid level foundation 2 Support all piping connected to pump 3 Wrap 1 1 2 to 2 layers of Teflon tape clockwise as you face end of pipe on all male thre...

Страница 6: ...diagram on motor nameplate If nameplate diagram differs from diagrams above follow nameplate diagram 7 If this procedure or the wiring diagrams are confusing consult a licensed electrician NOTICE Pump...

Страница 7: ...cal lift due to friction losses in pipe If no water is produced within 10 minutes stop pump release all pressure remove priming plug refill and try again Risk of explosion and scalding NEVER run pump...

Страница 8: ...cuit breaker DISCONNECT POWER Replace starting switch Refer to instructions on wiring DISCONNECT POWER check and tighten all wiring Refer to instructions on wiring Check with power company Install hea...

Страница 9: ...ice at 1 877 326 3561 For parts or assistance call ECO FLO Customer Service at 1 877 326 3561 REPAIR PARTS 1 2 3 4 NO QUANTITY PART NUMBER DESCRIPTION 1 1 EFLS15007 O Ring Diffuser 2 1 EFLS15008 O Rin...

Страница 10: ...defect Manufacturer will subsequently take corrective action as promptly as reasonably pos sible No requests for service will be accepted if received more than 30 days after the warranty expires Warra...

Страница 11: ...Manuel d utilisateur Les pompes d Arrosage de Pelouse S curit g n rale 12 Installation 13 15 lectricit 16 Fonctionnement 17 D pannage 18 Pi ces de r paration 19 Garantie 20 TABLE DES MATI RES...

Страница 12: ...s curit locales ainsi que la norme lectrique am ricaine NEC et la loi sur l hygi ne et la s curit au travail OSHA Remplacez imm diatement un cordon d alimentation en dommag ou us Ne pincez pas le c bl...

Страница 13: ...2 Des tron ons longs et de nombreux raccords aug mentent le frottement et r duisent l coulement de l eau vers la pompe Positionnez la pompe aussi pr s que possible de la source de l eau Utili sez aus...

Страница 14: ...un clapet de pied avec cr pine sur le tuyau en PVC 2 Installez un clapet anti retour dans le tuyau horizontal B Tron on horizontal de la surface de l eau la pompe 1 Fixez un clapet de pied au tuyau en...

Страница 15: ...as avec exc s 5 Remplacez le bouchon d amor age par un Cela va aider pour le calibrage de zones le d pan nage et le suivi de performance de la pompe AVIS En cas de longs tron ons horizontaux de tuyaut...

Страница 16: ...ur selon le sch ma port sur sa plaque signal tique S il diff re du sch ma donn plus haut fiez vous celui de la plaque signal tique 7 Si cette proc dure ou le sch ma de c blage ne sont pas clairs consu...

Страница 17: ...ION Amor age de la pompe AVIS L amor age veut dire l expulsion de tout l air du sys t me et le commencement de l attraction d eau depuis sa source Le terme ne concerne pas que le versement d eau dans...

Страница 18: ...y a pas d eau qui sort Arr tez la pompe puis contr lez le bon fonc tionnement de l amor age avant de chercher d autres causes D vissez le bouchon d amor age et v rifiez s il y a bien de l eau dans le...

Страница 19: ...t l phonez au Service de clientele de ECO FLO 1 877 326 3561 1 2 3 4 NO QUANTIT N DE PI CE DESCRIPTION 1 1 EFLS15007 O Ring Diffuser 2 1 EFLS15008 O Ring Housing 3 3 EFLS15009 Bolt 4 1 EFLS15005 Diff...

Страница 20: ...apr s la d couverte de tout d faut suppos Le constructeur ex cutera ensuite une action corrective dans un d lai raisonnable Aucune demande au titre de la garantie ne sera accept e si elle est re ue pl...

Страница 21: ...Manual del Usuario Bombas de la regadera del c sped Seguridad general 22 Instalaci n 23 25 El ctrico 26 Operaci n 27 Soluci n de problemas 28 Piezas de reparaci n 29 Garant a 30 Tabla del Contenido...

Страница 22: ...rmita que el cable haga contacto con aceite grasa superficies calientes o qu micos Conecte el motor a la fuente de energ a adecuada Vea la placa del motor y los diagramas de cableado y revise el volta...

Страница 23: ...a altas temperaturas y est n demasiado calientes al tacto Est n protegidos contra da os por calor durante el funcionamiento por medio de un interruptor interno de corte autom tico Antes de manipular...

Страница 24: ...a la bomba 1 V lvula de pie con filtro conectado a la tuber a de PVC 2 Instale la v lvula de retenci n en la tuber a horizontal B Horizontal del agua superficial a la bomba 1 Conecte la v lvula de pie...

Страница 25: ...bado por un indicador de presi n Esto ayudar a calibrar las zonas resolver problemas y cumplir los valores del cuadro de desem pe o de la bomba AVISO Para tramos de tuber a horizontales largos instale...

Страница 26: ...EL CABLEADO DE LA BOMBA PARA EL VOLTAJE INCORRECTO PROVOCAR DA OS EN LA BOMBA Plate Screws Motor Cover Plate 4 Utilice calibres de cables seg n las especificaciones del Cuadro de Cableado De ser posib...

Страница 27: ...la tuber a Si no sale agua en 10 minutos pare la bomba alivie la presi n retire el tap n para cebado vuelva a llenar y trate otra vez Riesgo de explosiones y quemaduras NUNCA haga funcionar la bomba c...

Страница 28: ......

Страница 29: ...QUANTITY PART NUMBER DESCRIPTION 1 1 EFLS15007 O Ring Diffuser 2 1 EFLS15008 O Ring Housing 3 3 EFLS15009 Bolt 4 1 EFLS15005 Diffuser Para obtener repuestos o asistencia llame a ECO FLO Servicio al Cl...

Страница 30: ...mente despu s del descubrimiento de cualquier supuesto defecto El fabricante tomar luego la acci n correctiva tan pronto como sea razonablemente posible No se aceptar n solicitudes de servicio si se r...

Отзывы: