background image

ERDRC-EC

ERDRC-EC

Installation Guide

Product Overview

Echoflex’s  lighting  controllers  use  wireless  technology  to  monitor  the  room’s 

environment eliminating much of the wiring normally required for distributed 

control. This translates into quick installations with less disruption to occupants 

allowing  facilities  to  accelerate  retrofit  schedules  and  start  saving  money 

sooner. The lighting controllers have Echoflex’s Smart Click technology which 

allows installers and facility operators to manage configuration settings without 

any tools reducing call-backs and installation expense. Using just a wireless wall 

switch,  the  facility  maintenance  engineer  can  adjust  setting  on  the  installed 

controllers eliminating a service call to an electrician.
This guide covers model number ERDRC-ECC which is equipped with an EnOcean 

315 MHz radio and the ERDRC-ECY equipped with a 868 MHz radio.
The package includes the ERDRC controller and installation guide.

ERDRC Operation

The ERDRC is a controller that can activate lighting loads when a received input 

from a linked sensor or switch is changed. 
As a lighting controller, the ERDRC operates lights based on:

•  ambient light levels monitored by an Echoflex light sensor
•  occupancy state monitored by Echoflex motion sensors
•  switch action from an Echoflex wall switch

Содержание ERDRC-EC

Страница 1: ...l backs and installation expense Using just a wireless wall switch the facility maintenance engineer can adjust setting on the installed controllers eliminating a service call to an electrician This g...

Страница 2: ...d while the light s are on and the timer is counting down an additional period of time is added to the timer total For example if the timer setting is 1 hour and the user pressed the switch ON twice t...

Страница 3: ...ights turn off There are 6 settings for this time out period The time out period is 15 minutes by default but can be set to a value of 5 to 25 minutes in 5 minute increments see the configuration sect...

Страница 4: ...draw 100 feet 30m diameter circles to identify optimal transmitter and controller locations Refer to the table for range considerations with other building materials Material Attenuation Material Ran...

Страница 5: ...o go around the obstacle Do not locate receivers close to other high frequency transmitters Leave at least 2 between the receiver and any other source of interference including lighting ballasts compu...

Страница 6: ...hes remotely Using the ERDRC with a wired wall switch If the circuit will have an additional hard wired switch wire the ERDRC in series before the switch Wiring Instructions Power to the controller is...

Страница 7: ...ill remain lit for 4 seconds while it links the new device It will resume toggling allowing you to link another device up to a total of 20 devices Linking a switch or sensor that is already linked to...

Страница 8: ...controllers relay off lights off to ignore the Simple Tap changes Simple Tap allows you to Enable or disable the motion sensor Auto ON feature Set the motion sensor Auto OFF timer Set the Light ON OFF...

Страница 9: ...ff until the light level decreases to the minimum dimming set point where the relay will close lights ON and the dimming output will increase as the natural light decreases Control Response with Dimmi...

Страница 10: ...bled the absolute value selected becomes the maximum dimming set point If the output is disabled the absolute value selected becomes the Light ON Set point With the light on tap the light sensors teac...

Страница 11: ...P A5 11 01 DB_3 Illumination 0 510lx linear n 0 255 DB_2 Illumination Set Point Min Max linear n 0 255 DB_1 Dimming Output Level Min Max linear n 0 255 DB_0 BIT_7 Repeater 0b0 disabled 0b1 enabled DB_...

Страница 12: ...ure the controller parameters Entering Smart Click Configuration Mode It is important to have feedback light from the ERDRC controller during configuration Using a linked switch see above turn the lig...

Страница 13: ...me blinking three times To exit Smart Click press OFF for 5 seconds Status Telegram the ERDRC can broadcast a status telegram per EEP A5 11 01 The telegram will broadcast every 100 seconds Refer to th...

Страница 14: ...figuration mode and click the switch ON or OFF until the light is blinking six times Press ON for 3 seconds If the auto on function is enabled the light will turn ON if disabled the light will be OFF...

Страница 15: ...ng eight times Press ON for 3 seconds Default setting is 60 of the light sensors full range If the dimming output is enabled there are 10 steps from 10 to 100 the light will blink the step count If th...

Страница 16: ...nking ten times This concludes the configuration directions for the ERDRC controller Echoflex Solutions Inc 1 38924 Queens Way Squamish BC Canada V8B 0K8 Toll Free 888 324 6359 Phone 778 733 0111 Fax...