56
Maintaining a Power Line Repeating Network
2.
Select one or more devices from the tree to be decommissioned.
•
To select one device, click that device.
•
To select multiple devices and perform a batch upgrade, click one device and then either hold
down CTRL and click all other devices to be decommissioned or hold down SHIFT and select
another device to decommission the entire range of devices. The
Setup - LON Device
Driver
Web page opens.
3.
Right-click a selected device, point to
Manage
, and click
Decommission
.
Alternatively, you can change the
Commission Status
property to
Uncommissioned
in the
Setup - LON Device Driver
Web page, which appears when you select devices in step 3.
4.
The SmartServer places the devices in the soft-offline state (the device has an application loaded
and is configured, but it is offline) and then unconfigures the devices. The offline devices are
highlighted red in the SmartServer tree and in the
Power Line Repeating Analysis
Web page.
5.
To recommission an unconfigured device and place it back online, select one or more devices to
recommission, right-click a selected device, point to
Manage
, and then click
Commission
on the
shortcut menu. You then select the devices again, right-click a selected device, point to
Manage
,
and then click
Set Online
on the shortcut menu.
Alternatively, you can select the
Smart Network Management
check boxes for the
Commission
Status
and
Application Status
properties in the
Setup - LON Device Driver
Web page, and then
click
Submit
. You can also change the
Commission Status
property to
Commissioned
and
change the
Application Status
property to
Application Running (Online)
, and then click
Submit
.
Note:
Changing the domain ID of the SmartServer causes all the devices on the network to be
recommissioned automatically and reconfigured to the new domain ID.
Setting Devices Offline
You can set a device on a power line repeating channel to the offline state in order to stop running its
application. This may be useful for testing the behavior of other devices on the network. An offline
device still receives data point updates; however, it does not process them. Instead, the offline device
transmits the default values for its data points. In addition, an offline device can still process
commission, decommission, set online, query status, clear status, wink and reset commands.
Note
: Setting a device offline may affect the performance of the power line repeating network,
particularly if the device is being used as a repeating agent in a repeating chain. If a repeating agent is