WRAS APPROVED FILLING LOOP
Subject
Description
Part Function
It is used for filling water to the central heating system.
Impact in Case of
Faulty Operation
1- No water is filled into combi boiler.
2- It cannot be turned off when filling water to boiler, and it causes
water discharge by opening safety valve.
3- It leads to mixing of tap water with the water in the central heating
system.
4- Where the pressure of main tap water system is very low, it may
cause low pressure error by emptying water in the central heating
system due to a faulty valve.
Primary Relevant
Error Codes
F40, F37
Troubleshooting and
Testing Method
Visual Inspection and Testing:
1- Checking whether there is any dirt, burrs, wear, deformation, etc.
on filling loop o-ring and filter.
Maintenance Period
Once a year filter cleaning, according to informations above.
Filter
PLUME KIT ASSEMBLY
For Plume kit installation, follow the instructions in the image below, you must disassemble the
part
at the end
of the horizontal flue kit (7006991167) and assemble with the Plume kit (700991251).
Do not disassemble this part
"A"
in case of single horizontal flue kit usage.
A
Figure
3
.
Plume Kıt
81
Table
3
2