Subject
Descrip
�
on
Part's Function
It is the component on which the gas + air mixture exits and on
which flame is formed.
Impact in Case of
Malfunction
1- Irregularity in the boiler emissions
2- Explosive burning
3- Flame loss
Main Associated Error
Codes
E01, E82, "Flame Loss Risk" warning
Diagnostics and Test
Method
Visual Control: Closed hole on the burner, oxidation,
deformation, etc. cleaning with a non-metallic brush.
• Burner
Table
12
63
Содержание CONFEO PREMIX P 14 HM
Страница 1: ...SERVICE MANUAL CONFEO PREMIX CONDENSING BOILER CONFEO PREMIX P 14 20 24 28 30 35 HM HCH HST...
Страница 24: ...12 ELECTRICAL DIAGRAM Figure 15 24...
Страница 34: ...Low Voltage Removing installing the pump cable FAN PWM CABLE Figure 39 Figure 40 34...
Страница 52: ...Figure 76 Figure 77 52...
Страница 83: ......