19)
EBARA
Corporation
4.3.2 Power Supply Wiring
WARNING
Use the correct wiring materials and size to match the operating conditions in
accordance with the power consumption rating and ambient air temperature of
the pump.
CAUTION
Be sure to connect the grounding wire.
CAUTION
Wiring should be hard-wired or using twist-lock Hubbel-type connector at power
source side.
Wire the connector for the main power supply. Fig. 4.4 and Tables 4.2 and 4.3
show the connector pin assignment.
Table 4.3
Terminal Block
Specification
Pump model
Model ESA70W(N)
Receptacle type
JL04HV-2E22-22PE-B
Recep. Manufacturer
Japan Aviation Electronics Industry Co., Ltd.
Adapted plug type
JL04V-6A22-22SE-EB
Suitable wire
UL1015 AWG #10
* Lengthen grounding wiring 1.2m from other wiring(R,S,T).
D A
C B
No.
Phase
A
R
B
S
C
T
D
GND
Table 4.2 Pin Assignment
of Power Supply Terminal Block
Fig 4.4 Power Supply Terminal Block
(As seen from connecting side)