Using the remote controls                                                                                    

The control board can accept diff erent type of codes, the fi rst memorized remote control defi nes the type, consequently, other 

type of codes (diff erent from the fi rst memorized remote control) cannot be learnt. The control board accepts standard codes 

from 12 to 64 bit and only the fi xed part of the code for the rolling code HCS©, but using the DIP 3-B the rolling code counter 

can be monitored. This way the remote controls cannot be copied. The memory capacity is about 200 diff erent rolling codes. 

The fi rst memorized remote control defi nes the type of code that the receiver shall learn, consequently, the subsequently 

memorized remote controls must have the same type of code. 

This operation cancels all previous memorized codes. It is not contemplated the cancellation of a single remote 

control code. It is necessary to reset the memory before learning the fi rst remote control to avoid the remaining 

of previously memorized codes that aren’t in use in the installation.

The cancellation of the memory (all codes) is possible only when the gate is closed. 

1

Make sure that the gate is in 

CLOSED

 position. 

Press and keep pressed the codes button

2

Wait for the 

L.E.D. CODES 

to start fl ashing, then release it.

Wait until the reset of the memory. 

6.1 

FULL CANCELLATION of the memory

 CODES

 CODES

6.2 

Learning of the remote controls

The remote controls can be learnt ONLY when the gate is 

CLOSED

PERFORM ThE LEARNING WIThOUT CONNECTING ThE ANTENNA TO ThE CLAMPS NO. 17-18

- If you need to learn a new remote control repeat the same operation.

- When you push the remote control’s button and the L.E.D. codes is switched ON, it means that the remote control is not 

  compatible.

- When you push the remote control’s button and the L.E.D. codes fl ashes slowly, it means that the memory is FULL.

- In this card is not previewed the cancellation of a single remote control ‘s code. 

1

Make sure that the gate is in 

CLOSED

 position.

          >

2

Press and release the 

CODES

 button, the 

LED CODES 

will stay lit. 

3

Press the button of the remote control, ex: button no.1: 

if it is memorized 

L.E.D. CODES

 will fl ash

           >

1

Press and release the CODES button, the 

L.E.D. CODES

 will stay lit. 

           >

2

Press again the CODES button, the

 LED CODES

 will fl ash and stay lit

3

Press the button of the remote control, ex: 

button no.2: if it is memorized 

L.E.D. CODES

 will fl ash

CODES

CODES

CODES

START-S4XL

Technical manual

-16-

START

PEDESTRIAN

Содержание NOLOGO START-S4XL

Страница 1: ...photocell START 24 Vac 24 Vac 12Vac elect lock 12Vac elect lock STOP 26 27 Light Lamp Light Lamp 28 29 Phototest 24 Vac 12 Vac Lamp or courtesy light 230Vac Ground Connection 2 9 10 11 Motor 2 COMMON...

Страница 2: ...hat you contact the competent public agencies the waste collection service or the shop where you purchased the product Small legend OLS Open limit switch CLS Close limit switch START Control to drive...

Страница 3: ...e products 1 1 Safety precautions Read carefully the manual Read carefully the manual before installing 1 2 Symbols and warning 1 3 Security System 1 Introduction It is important to establish the MACH...

Страница 4: ...ible clamps It was created to suit various needs both for door gates and sliding gates The design adopted the most advanced techniques to guarantee the utmost immunity vs noises the maximum operating...

Страница 5: ...must be jumpered to the common If the same input has more than one contact NC they are placed in series If they are not used the inputs to the Normally Open NO contacts are left loose If the same inpu...

Страница 6: ...s Neutral 230Vac Ground Phase 230Vac Lamp 230Vac Lamp 230Vac MOT 1 COM MOT 1 OPEN MOT 1 CLOSE MOT 2 COM MOT 2 OPEN MOT 2 CLOSE LSC MOT 2 LSO MOT 2 LSC MOT 1 LSO MOT 1 Photo A only cl START 24 Vac 12 V...

Страница 7: ...Switches motor no 1 LSO M1 15 Input Opening Limit Switches motor no 1 Photocell A 16 Input photocell A working only by closing see chapter 2 3 START 17 Input command bi stable START 24Vac 18 Output f...

Страница 8: ...test on the photocells or for a 24V light you can t use this connection 4 6 Connection of a 24Vdc light with an open and moving gate 28 29 30 31 20 21 If you are expecting to use the test on the photo...

Страница 9: ...3 4 5 Light Group 230 Vac DIP 4 A ON If you are using a piece of stiff wire instead of an an tenna to obtain a 433Mhz frequency you have to cut it off to 17 cm e connect it to the clamp no 25 coaxial...

Страница 10: ...ommand connection on the clamp no 17 connect in parallel The connection of the command for pedestrian opening can be realized on every button or contact as soon as it is type N O normally opened 4 12...

Страница 11: ...EST on the photocells can only ensures the correct working of the automation if said photocells are regularly working The control board will perform a test before every opening In case of malfunction...

Страница 12: ...power supply voltage type N C normally closed POWER SUPPLY RX PHOTOCELL Receiver photocell Clamps contact N C When the control board is powered the led lights that are placed on the inputs are lit up...

Страница 13: ...e output of the terminal board 4 and 5 there is tension at the beginning of the opening till 2 minutes before closing useful to power the courtesy light 5 ON Pre lighting It ables the pre lighting bef...

Страница 14: ...m force for the start and they can reach the planned values This function is not compatible with all gates it should be evaluated according to the installation 5 ON 1 motor It able the use of only one...

Страница 15: ...SC M2 12 Exclusion of the inputs closes limit switches motor no 2 2 ON LSO M2 13 Exclusion of the inputs opens limit switches motor n 2 3 ON LSC M1 14 Exclusion of the inputs of the closing limit swit...

Страница 16: ...t the gate is in CLOSED position Press and keep pressed the codes button 2 Wait for the L E D CODES to start flashing then release it Wait until the reset of the memory 6 1 FULL CANCELLATION of the me...

Страница 17: ...the TIMES button or START if the limit switches are not available The second motor stops wait until the first motor stops END OF LEARNING TIME if the limit switches are available wait until both moto...

Страница 18: ...pause time starts Let the required pause time run 7 Push the TIMES button or START The second motor CLOSES 8 Push the TIMES button or START if the slowing down is activated trimmer see Slow down The...

Страница 19: ...tor no 1 stops The pedestrian door is closed End 4 a If the limit switch is available wait until the motor no 1 pedestrian use stops in its closing Motor no 1 stops by closing limit switches The pedes...

Страница 20: ...rs can be delayed Connect for the TEST 1 When the control is switched OFF put in OFF dip 8 of DIP A 2 Power the control unit and wait the standard flash of the Led 3 Put in ON DIP 8 of DIP A 4 Let the...

Страница 21: ...PEN CLOSE CODES OPEN CLOSE CODES Led indicating the opening is switching on The gate is opening OPEN CLOSE CODES Led opening and closing flashes The gate is open and stop OPEN CLOSE CODES Legend Despl...

Страница 22: ...10 Note START S4XL Technical manual 22...

Страница 23: ...PRODUCT COMPLIES with what is outlined in the European Community directives 2006 95 CE EEC DIRECTIVE 2006 95 ISSUED BY THE EUROPEAN COUNCIL on December 12 2006 harmonizing the legislation of the membe...

Страница 24: ...n est pr sent e sous la seule responsabili du constructeur et si applica ble de son repr sentant autoris Busto Arsizio Va Italia 14 06 2007 ERNESTINO BANDERA Administrateur KONFORMIT TSZERTIFIKAT Der...

Отзывы: