5 Installation
5.3 Interfaces
MICRO PANEL XV200
10/2011 MN04802007Z-EN
www.eaton.com
27
5.3.3
Power supply
The device is provided with an internal self-resetting fuse and is protected against polarity reversal. The
functional earthing terminal is connected exclusively to the connector cover and not to the 0 V. The
housing is made from plastic and is isolated. The device power supply is
not
electrically isolated.
The device requires a 24 VDC power supply from an AC/DC converter with safe isolation (SELV). For
other power supply requirements see Chapter 9.5.1 Power supply,
589.5.1 Power supply,
58.
SELV (safety extra low voltage):
Circuit in which no dangerous voltage is present, even in the event of a single fault.
Wiring
Phoenix Contact MSTB 2.5/3-ST-5.08 connector, Phoenix order no. 1757022 is supplied with the
device.
Tab. 5 Assignment of connector
The following must be observed when the connector wiring is prepared:
Tab. 6 Preparing the wiring of the connector
Fig. 7 Power supply interface
Fig. 8 Phoenix Contact MSTB 2.5/3-ST-5.08 connector (view from the wiring side)
Connection
Assignment
+24 VDC
+24 VDC power supply
Functional earthing connected with connector cover.
Does not have to be connected.
This connection can be used as protective earthing connection if the
mounting environment requires this.
0 V
0 V power supply
Preparing the wiring of the connector
Terminal type
Pluggable screw terminal
Cross-section
min. 0.75 mm
2
/ max. 2.5 mm
2
(lead or wire)
min. AWG18 / max. AWG12
Stripping length
7 mm
Max. tightening torque
0.6…0.8 Nm / 5…7 Lb. In.
0 V
+24 VDC
Содержание XV200
Страница 1: ...Operating Instructions 10 2011 MN04802007Z EN replaces M001089 08 03 2010 XV200 MICRO PANEL...
Страница 6: ...1 General 1 3 Additional documentation 6 MICRO PANEL XV200 10 2011 MN04802007Z EN www eaton com...
Страница 10: ...2 Device description 2 7 Designation 10 MICRO PANEL XV200 10 2011 MN04802007Z EN www eaton com...
Страница 18: ...3 Safety regulations 3 4 Device related hazards 18 MICRO PANEL XV200 10 2011 MN04802007Z EN www eaton com...
Страница 20: ...4 Operating and indication elements 4 1 Overview 20 MICRO PANEL XV200 10 2011 MN04802007Z EN www eaton com...
Страница 42: ...5 Installation 5 4 Mounting 42 MICRO PANEL XV200 10 2011 MN04802007Z EN www eaton com...
Страница 46: ...6 Operation 6 3 Switching off the device 46 MICRO PANEL XV200 10 2011 MN04802007Z EN www eaton com...
Страница 52: ...7 Maintenance and service 7 4 Troubleshooting 52 MICRO PANEL XV200 10 2011 MN04802007Z EN www eaton com...