5 Installation
5.3 Interfaces
MICRO PANEL XV200
10/2011 MN04802007Z-EN
www.eaton.com
37
Fig. 16 Alternative termination (only for XV200, MK2)
The bus segment must be terminated at both ends.
No more than two terminations must be provided on each bus segment.
At least one of the two terminations must be fed by the bus station.
Transmission faults can occur if operation is carried out without the correct termina-
tion on the Profibus network.