EATON XSTORAGE COMPACT INSTALLATION MANUAL
P-16400097 - September 2020 www.eaton.com
39
b.
For CAN cabling in a rack with two battery strings, connect the Com IN and Com OUT cables
as in Figure 21: CAN cabling in the external battery rack with two battery strings.
Figure 21. CAN cabling in the external battery rack with two battery strings
c. Make sure that the small termination resistor switch is in the bottom position (resistor
connected) in the primary battery pack of the external battery rack. Make sure that the small
termination resistor switch is in the top position (resistor not connected) in the primary battery
pack in xStorage Compact.
d.
For the primary battery pack and battery pack addresses, see
Table 12. Primary battery pack
and battery pack addresses (hexacode)
.
4. Connect the external battery rack to xStorage Compact. For connections on the ESS side, refer to
Section 5.4.1 AC and DC cable connections.
For details on wiring on the external battery rack side, see
Table 13. Wiring between the primary