EATON XSTORAGE COMPACT INSTALLATION MANUAL
P-16400097 - September 2020 www.eaton.com
32
Figure 14. Communication interfaces
Table 9. Communication interface terminals
Interface protection and customer I/Os
Internal communication
connections
Battery breaker status
signals
PIN
X7
X8
X9
1*
Dry-contact relay output (NO)
CAN H (PCS)
CB1_UVR
2*
Customer relay output (common)
CAN L (PCS)
CB2_UVR
3
Interface protection input_1
CAN GND (PCS)
CB3_UVR
4
Interface protection input_2
CAN H (Battery pack)
CB1_UVR_0V
5
Interface protection input_3
CAN L (Battry pack)
CB2_UVR_0V
6
Interface prot24VDC
CAN GND (Battery pack)
CB3_UVR_0V
7
Digital output_1
12 VDC_Wake-up
CB1_STATE_11
8
Digital output_1_0V
12 VDC
CB1_STATE_14
9
Digital output_2
12 VDC_Contactor
CB2_STATE_11
10
Digital output_2_0V
0 V_Contactor
CB2_STATE_14
11
Digital output_3
SPD_State
CB3_STATE_21
12
Digital output_3_0V
SPD_+24VDC
CB3_STATE_24
* Dry contact relay output rated for 24 VDC max. 6 A.
5.6.1
Customer communication interface
There is a Modbus TCP/IP interface available for a customer communication. Connect the RJ45 cable
from the external customer connectivity gateway to the Ethernet interface terminal ETH-2 (see
Figure 14.
Communication interfaces
. Category 5 cable is recommended to use for connecting.