EATON XSTORAGE COMPACT INSTALLATION MANUAL
P-16400097 - September 2020 www.eaton.com
29
11. Attach PE cables between each battery pack and the battery rack.
PE cabling of battery packs cannot be chained. Each pack must have a separate 16 mm
2
PE cable
to the frame. The tightening torque is 10 Nm.
5.4
AC and DC cabling of the energy storage system
To gain access to the terminal blocks, remove the screws securing the gland plates of the ESS cabinet.
Install suitable cable glands into the gland plate and route the cables through the glands.
Figure 11. Gland plates at the top and bottom of the unit
1
I/O cable glands
2
Signal cable glands
Connect the cables to the respective terminal blocks inside the ESS.