5 Installation
5.4 Preparing the device for operation
42
MICRO PANEL XP-702
07/2011 MN04802003Z-EN
www.eaton.com
5.4
Preparing the device for operation
1
Check the device for damage in transit.
2
If required, fit the required PCI expansion card in the device. See Chapter 5.4.1 Fitting a PCI
expansion card in the device,
3
Fit the mass storage memory (CF cards and/or hard disk) in the device:
Fitting the CF card, see Chapter 5.4.2,
Fitting the hard disk, see Chapter 5.4.3,
4
With 1.8 GHz devices (XP-702-D…, XP-702-F…), fit an active cooling unit to the rear of the device.
See Chapter 5.4.4 Mounting the active cooling unit,
5
Mount the device in the control cabinet, control panel or the control desk (BOX devices only in
control cabinets):
Devices with display, see Chapter 5.4.5 Mounting a device with a display,
BOX devices, see Chapter 5.4.6 Mounting a BOX device,
56.
CAUTION
Operational malfunctions
Use of unsuitable or improperly prepared cables, as well as incorrect wiring will
mean that neither the values stated in the technical data nor the electromagnetic
compatibility (EMC) can be ensured.
Only use cables prepared by specialists.
The cables used must be prepared according to the interface description in this
document.
The wiring instructions for the relevant interface must be observed when wiring
the device.
Any generally applicable regulations and standards must be fulfilled.
CAUTION
Device condensation
If the device is or was exposed to climatic changes (temperature fluctuation, air hu-
midity) moisture can form on or in the device (device condensation). In this case,
there is a risk of short-circuit.
The device must
not
be switched on when device condensation is present.
If condensation is present on the device, or if it was exposed to temperature fluc-
tuations, it must be allowed to adjust to room temperature (do not expose the de-
vice to the direct heat of heating devices) prior to commissioning.
Required depending on device version and operating system used:
CF card with operating system (for Windows XPe)
Hard disk with operating system (for Windows XP)
Active cooling unit (for devices with 1.8 GHz (XP-702-D…, XP-702-F…)
The device must only be installed and commissioned in perfect technical condition and
in compliance with this document.