XAP Series Busduct

Storage, Installation, and Maintenance

Tap-off Unit Inspection

When inspecting and performing maintenance on tap-off units, ensure 

the breaker is in the open position and that the power to the busduct is 

turned off.

1. Make sure the breaker is in the open position;

2. Turn off power to the busduct;

3. Using a multi-function meter, open the tap-off unit door and check to 

ensure there is no voltage present on the line side of the unit;

4. For fusible units, check the fuse clip contact pressure and contact 

means. If there are any sign of over-heating, replace fuse clips;

5. Look for any signs of deterioration of insulating materials and 

protective barriers;

6. Check the operation of all mechanical components.

7. Check the mechanisms of all electrical and mechanical interlocks 

and padlocking means;

8. Check for missing or broken parts, rusting, corrosion, dirt, and 

excessive wear;

9. Check the line and load connections to ensure proper torque.

10. Clean off any arc spatter or soot deposits;

11. Replace any damaged parts;

12. Operate each switch or circuit breaker several times to ensure 

proper working order.

Note

These maintenance instructions and procedures do not represent an 

exhaustive list of maintenance steps required to maintain safe 

operation of the busduct and tap-off units under all applications. 

Specific applications may require additional steps and procedures. For 

additional information or assistance with issues not covered sufficiently 

in this publication, contact the local Eaton sales office.

 

 DANGER

HAZARD OF ELECTRICAL SHOCK OR BURN. TURN THE POWER TO THE
BUSDUCT OFF BEFORE INSTALLING, REMOVING, OR WORKING ON THIS 
EQUIPMENT.

 WARNING

RECOGNIZED SAFETY PROCEDURES MUST BE FOLLOWED PRIOR TO ANY
WORK OR MAINTENANCE BEING PERFORMED.

Содержание XAP Series

Страница 1: ...xpansion Joint Installation End Cover Installation Settlement Joint Installation Horizontal Mounting Vertical Mounting Wall Penetrations Busduct Joint Clearances Tap off Unit Installation Attentions f...

Страница 2: ...tored in a covered clean dry space which is climate controlled to prevent condensation Do not allow the busduct to come in contact with corrosive fumes liquids salts or forms of concrete Storing the b...

Страница 3: ...ion When connecting pieces of the Eaton XAP busduct together make certain that contact surfaces are clean and free from contaminants Some section may have electrical lubricant on the contact surfaces...

Страница 4: ...the installation drawing Notes after completion of one line installation it is necessary to loosen all M6 25 bolts in the expansion joints to ensure expansion effect see Figure 7 Figure 7 Expansion J...

Страница 5: ...dened at the joints 3 Care should be given when locating drop rods in order to avoid placing hangers at joint and tap off unit locations Adequate ceiling clearance must be allowed for tap off units Ve...

Страница 6: ...able to avoid movement 2 Tap off unit shall not be burdened with load directly Loads at the rear end shall be fastened onto the busduct or other fixed positions in accordance with regulations 3 When n...

Страница 7: ...st be kept clean during installation 2 Busducts must be adjusted and kept in the same line before fastening the bolts of joint units Tolerance of assembly in horizon and vertical direction are 5mm per...

Страница 8: ...the mechanisms of all electrical and mechanical interlocks and padlocking means 8 Check for missing or broken parts rusting corrosion dirt and excessive wear 9 Check the line and load connections to e...

Страница 9: ...the environment through the use of power management technologies and services Eaton has approximately 95 000 employees and sells products to customers in more than 175 countries For more information...

Отзывы: