background image

4

Maximum clearance loading weight (kg

Mounting clearance (m) 

XAP-C (kg/m)

XAP-A (kg/m)

1.2

50.4

50.4

1.6

22.6 

 50.4

22.6 

 50.4

2

22.6

22.6

EATON  CORPORATION

  

www.eaton.com.cn/electrical

Instruction Booklet IB

Effective January 2017

XAP Series Busduct
Storage, Installation, and Maintenance

Horizontal Mounting

For over-head mounting of the Eaton XAP busduct, all-thread drop rods 

must be provided by the installer and should not be spaced more than 

2m apart.

1. The mounting clearance for straight busduct should not be longer 

than 2m. Detailed clearance requirements shall be requested during 

routing design according to field conditions and loading situations, 

and shall be specified in installation drawing.

2. Mounting supports shall be placed at both ends of the joint. 

Maximum clearance is no longer than 1m. No load shall be burdened 

at the joints.

3. Care should be given when locating drop rods in order to avoid 

placing hangers at joint and tap-off unit locations. Adequate ceiling 

clearance must be allowed for tap-off units.

Vertical Mounting

For mounting the busduct vertically, vertical spring hangers must be 

used. A vertical hanger must be used on every floor or a   maximum of 

every 16 ft. (4.9m). Intermediate hangers are required for floor heights 

exceeding 16 ft. (4.9m) as shown in Fig. 10.

Maximum tolerance for busduct installation is 5mm per 10m.

Figure 10. Vertical Busduct Mounting Support

Wall Penetrations

When an Eaton XAP busduct passes through a wall or vertical barrier, 

the opening should be at least 100 mm larger than the outside 

dimensions of the busduct.

For individual and multiple runs of Eaton XAP busduct, thought must be 

given to horizontal and vertical clearances between runs, walls, and 

ceilings.

Figure 11. Horizontal Wall Penetration Installation

Figure 12. Vertical Floor Penetration Installation

 

 

 

Busduct

Busduct

Busduct

Busduct

Содержание XAP Series

Страница 1: ...xpansion Joint Installation End Cover Installation Settlement Joint Installation Horizontal Mounting Vertical Mounting Wall Penetrations Busduct Joint Clearances Tap off Unit Installation Attentions f...

Страница 2: ...tored in a covered clean dry space which is climate controlled to prevent condensation Do not allow the busduct to come in contact with corrosive fumes liquids salts or forms of concrete Storing the b...

Страница 3: ...ion When connecting pieces of the Eaton XAP busduct together make certain that contact surfaces are clean and free from contaminants Some section may have electrical lubricant on the contact surfaces...

Страница 4: ...the installation drawing Notes after completion of one line installation it is necessary to loosen all M6 25 bolts in the expansion joints to ensure expansion effect see Figure 7 Figure 7 Expansion J...

Страница 5: ...dened at the joints 3 Care should be given when locating drop rods in order to avoid placing hangers at joint and tap off unit locations Adequate ceiling clearance must be allowed for tap off units Ve...

Страница 6: ...able to avoid movement 2 Tap off unit shall not be burdened with load directly Loads at the rear end shall be fastened onto the busduct or other fixed positions in accordance with regulations 3 When n...

Страница 7: ...st be kept clean during installation 2 Busducts must be adjusted and kept in the same line before fastening the bolts of joint units Tolerance of assembly in horizon and vertical direction are 5mm per...

Страница 8: ...the mechanisms of all electrical and mechanical interlocks and padlocking means 8 Check for missing or broken parts rusting corrosion dirt and excessive wear 9 Check the line and load connections to e...

Страница 9: ...the environment through the use of power management technologies and services Eaton has approximately 95 000 employees and sells products to customers in more than 175 countries For more information...

Отзывы: