XAP Series Busduct
Storage, Installation, and Maintenance

Installation

One set of construction drawings is sent with the initial shipment of 

each busduct order. This drawing package will contain the layout of each 

run, showing where each piece of the run is located, and other possible 

cut sheets and instructions. The installer should review these drawings 

prior to and during installation to ensure proper installation.

Identification

Each piece of the Eaton XAP busduct has a nameplate label as shown in 

Figure 1. This label identifies each piece and its ratings. It is recommend-

ed that each piece be installed sequentially, starting at the beginning 

point of the run. This would typically be the cable tap box, transformer, 

switchboard, or switchgear connection.

Figure 1.  Nameplate Label

Phasing and Orientation Labels

Each piece of the Eaton XAP busduct has “N” labels as shown.  The "N" 

label indicates phasing. From the “N” side of the busduct, the standard 

phasing is N-L3-L2-L1-PE.

Figure 2. Phasing and Orientation Label

The XAP busduct construction is not symmetrical. It is imperative for 

all sections of the busduct to be installed with all of the labels aligned 

and consistent throughout the run and per Eaton-supplied construction 

drawings. Failure to do so may result in damage to the busduct as well 

as property damage, physical harm or death.

Joint Installation

When connecting pieces of the Eaton XAP busduct together, make 

certain that contact surfaces are clean and free from contaminants. 

Some section may have electrical lubricant on the contact  surfaces, 

which was applied by the factory. This will aid in joint installation. Align 

the left end of one section to the right end of the adjoining section with 

the "N" label in alignment. Figure 3 illustrates correct joint installation.

Figure 3. Joint Installation

Torque Indication Bolt

When the two sections have been properly joined together, the joint 

bolt may be tightened. This joint bolt is a special torque-indicating bolt 

with two bolt heads to ensure that the proper installation torque is 

achieved. Fall away instruction tags are provided between the upper 

and lower bolt heads. Torque should only be applied to the upper bolt 

head. When the proper torque is achieved, this bolt head will shear off, 

allowing the tag to fall to the floor.

Figure 4. Torque Indicating Bolt as Shipped 

Figure 5. Torque Indication Bolt after Installation

Any joint bolt that is improperly tightened will retain the highly visible tag 

and should be retightened. The lower bolt head remains intact for future 

maintenance.

 DANGER

FAILURE TO INSTALL THE BUSDUCT CORRECTLY MAY RESULT IN 
DAMAGE TO THE BUSDUCT AS WELL AS PROPERTY DAMAGE, PHYSICAL 
HARM, OR DEATH.

L1

L3

L2

PE

N

L1

L3

L2

PE

N

Orange
instruction Tag

Figure 4.

Figure 5.

Compact Busway

Type

Standard

Name of contract

Contract No.

Installation No.

Manufacture Date

Principal/Producers

Production enterprise

Eaton Electrical Equipment Co.,LTD.

Chongqing Yiwan Electric Co., LTD.

Ue =

Ui =

V

V

A

kA

In =

Icw =

f =50/60Hz

IP65

<XAP>

IEC61439-1/-6

Содержание XAP Series

Страница 1: ...xpansion Joint Installation End Cover Installation Settlement Joint Installation Horizontal Mounting Vertical Mounting Wall Penetrations Busduct Joint Clearances Tap off Unit Installation Attentions f...

Страница 2: ...tored in a covered clean dry space which is climate controlled to prevent condensation Do not allow the busduct to come in contact with corrosive fumes liquids salts or forms of concrete Storing the b...

Страница 3: ...ion When connecting pieces of the Eaton XAP busduct together make certain that contact surfaces are clean and free from contaminants Some section may have electrical lubricant on the contact surfaces...

Страница 4: ...the installation drawing Notes after completion of one line installation it is necessary to loosen all M6 25 bolts in the expansion joints to ensure expansion effect see Figure 7 Figure 7 Expansion J...

Страница 5: ...dened at the joints 3 Care should be given when locating drop rods in order to avoid placing hangers at joint and tap off unit locations Adequate ceiling clearance must be allowed for tap off units Ve...

Страница 6: ...able to avoid movement 2 Tap off unit shall not be burdened with load directly Loads at the rear end shall be fastened onto the busduct or other fixed positions in accordance with regulations 3 When n...

Страница 7: ...st be kept clean during installation 2 Busducts must be adjusted and kept in the same line before fastening the bolts of joint units Tolerance of assembly in horizon and vertical direction are 5mm per...

Страница 8: ...the mechanisms of all electrical and mechanical interlocks and padlocking means 8 Check for missing or broken parts rusting corrosion dirt and excessive wear 9 Check the line and load connections to e...

Страница 9: ...the environment through the use of power management technologies and services Eaton has approximately 95 000 employees and sells products to customers in more than 175 countries For more information...

Отзывы: