10. Technical Specification
10. Technical Specification
Power Supply and Charger
AC Input
230V AC +10%/-15%, 50Hz
Internal Power Supply
28V DC
Supply & Battery
Monitored Open, Short, Fuses
Protection
Deep Discharge, Short, Thermal
Temperature Compensation
YES
Battery Size and Type
2 x 12V VRSLA 5Ah (Check local regulations) (not supplied)
Mains Fuse
1.6A 250V anti surge
Battery Fuse
6.3A 250V anti surge
Max Charge Current
1A
Inputs
Number of Lines
5
Remote Enable
Short to use
End of Line
3K9
Outputs
Number
2, Fault & In Use
Type
Volt free relay
Contact
30V DC 1A
Controls
Buttons
6, five lines 1 fault ack
Zone LEDs
5 status, 5 Fault status
Fault LEDs
3, AC, DC General
Outstation Cables
Type
Please refer to local codes of practice
Cores
2 core 1mm or 1.5mm
Distance
500m max, with soft skinned cable
Dimensions (H x W x D)
EFVCC5
303mm x 433mm x 89mm
EFVCC5-FC
353mm x 483mm x 2.5mm
EFVCC5-FB
359mm x 490mm x 0.9mm
Weight
EFVCC5
5.45kg (without batteries)
EFVCC5 with EFVCC5-FC fitted
7.63kg (without batteries)
EFVCC5 with EFVCC5-FB fitted
6.05kg (without batteries)