3

Type VFI, Fluid-insulated Switchgear 

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

   MN285006EN   March 2018

Cabinet construction

Type VFI switchgear features deadfront, tamper-resistant, 

low-profile construction. It is suitable for operation in 

areas subject to excessive moisture, occasional flooding, 

and blowing snow. Cabinets meet the enclosure security 

requirements of IEEE Std C57.12.28™-2005 standard.
Top-hinged doors are provided with door stays and fitted 

with stainless steel hinges. On units wider than 1168 mm 

(46 in), split doors are provided to allow easy operation 

by one person. Side-hinged doors can also be provided as 

an option. Both source and tap doors can be fully open at 

the same time. Each door has a floating lock pocket with 

padlock provisions and a pentahead silicon bronze door bolt.
Tank construction is of 7- or 10-gauge steel and cabinets are 

made of 12 or 13-gauge steel. Recessed lifting provisions 

are provided at each corner of the tank for a balanced lift.

Table 1 .  Electrical ratings

Rating

5 kV

15 kV

25 kV

35 kV

Maximum Design Voltage, kV 

15.5

15.5

27

38

BIL, kV 

95

95

125

150

1-Minute Withstand (60 Hz) Interrupter* and Terminators, kV

35

35

60

70

Continuous Current (max), A 

600

600

600

600

Interrupting Current (sym./asym.), kA 

12/20

12/20

12/20

12/20

Momentary Current 10 cycles (asym.), kA 

20

20

20

20

1-Second Withstand Current (sym.), kA

12

12

12

12

Making Current (sym.), kA

12

12

12

12

Transformer Magnetizing Interrupting Current, A 

21

21

21

21

Cable Charging Interrupting Current, A

10

10

25

40

* The withstand rating of the switch is higher than that of the connectors per IEEE C37.74

TM

 2003 standard.

Padlocking provisions

Provisions are included for padlocking the cabinet in order 

to prevent unauthorized door opening. The cabinet must 

be locked at all times to prevent accidental contact with 

hazardous voltage.

Standard features

Standard features (refer to 

Figure 2

) include a fluid level 

indicator, automatic pressure-relief valve, operation one-line 

diagrams on the doors, fluid fill plug, fluid drain and sampler 

and a standoff bracket for each bushing. Standard ground 

provisions include a 1/2-13 UNC stainless steel ground nut 

for each bushing.

Interrupter duty cycle

The vacuum fault interrupter mechanism conforms to 

the duty cycle requirements of IEEE Std C37.60™-2003 

standard.

Switch test sequence

The vacuum fault interrupter operating mechanism conforms 

to the switch test sequence requirements of IEEE Std 

C37.74™-2003 standard.

Finish

VFI switchgear is finished in a green color which conforms 

to Munsell 7GY 3.29/1.5 Green. The coating conforms to 

the following specifications: IEEE Std C57.12.28™-2005 

standard, ASTM B1117 1000- hour 5% salt spray corrosion 

test, ASTM D2247 1000- hour humidity test, ASTM G53 

500-hour ultraviolet accelerated weathering test and ASTM 

D2794 impact test.

Nameplate

Prior to installation, be sure to check the switchgear 

nameplate on the tank front plate in the source side cabinet 

to verify that the voltage and current ratings are correct for 

the system on which the switchgear is to be installed.

Operating handles

 DANGER

Hazardous voltage . Never rely on the open position of 

the operating handle or the contact position indicator; 

it does not ensure that the line is de-energized . Follow 

all locally approved safety practices . Failure to comply 

can result in contact with high voltage, which will cause 

death or severe personal injury . 

G123 .1

Содержание VFI

Страница 1: ...Type VFI Fluid insulated Switchgear Installation Operation and Maintenance Instructions COOPER POWER SERIES Underground Distribution Switchgear MN285006EN Effective March 2018 Supersedes December 2015...

Страница 2: ...PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS D...

Страница 3: ...binet construction 3 Standard features 3 Interrupter duty cycle 3 Switch test sequence 3 Finish 3 Nameplate 3 Operating handles 3 Weight 4 Special certifications 4 INSTALLATION PROCEDURE 4 OPERATION 5...

Страница 4: ...hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION...

Страница 5: ...e pallet Improper handling can cause damage to the switchgear If the switchgear is to be stored for any appreciable time before installation provide a clean dry storage area Be careful during handling...

Страница 6: ...llation Operation and Maintenance Instructions for operation information for the RVAC switch Vacuum fault interrupters Load and fault interruption takes place within sealed vacuum interrupters Figure...

Страница 7: ...37 74TM 2003 standard Padlocking provisions Provisions are included for padlocking the cabinet in order to prevent unauthorized door opening The cabinet must be locked at all times to prevent accident...

Страница 8: ...tances where a UL listing is required Figure 3 VFI switchgear operating handle three phase ganged operation Figure 4 VFI switchgear operating handles single phase operation Installation procedure WARN...

Страница 9: ...T223 2 5 Ground switchgear Switchgear must be adequately grounded Install a permanent low resistance ground connection to the switchgear tank Grounding provisions are provided near the bottom of the t...

Страница 10: ...aintenance Instructions for operation information for the RVAC switch Loadbreak switch In most configurations a Type RVAC loadbreak switch is integrated within the VFI switchgear The switch s push to...

Страница 11: ...ith sampler at the bottom of the tank If moisture is found in the tank refill with clean dry insulating fluid WARNING Hazardous voltage This equipment must be de energized and grounded prior to conduc...

Страница 12: ...ry T239 2 Use the following fluid sampling guidelines to prevent contamination and to safely extract fluid samples 1 De energize and ground the switchgear prior to sampling fluid 2 Where local governi...

Страница 13: ...from altering the moisture content of the sample Leave about one inch of air space in the container to account for thermal expansion 15 Retighten sampling valve to finger tight plus a 1 4 turn Reinsta...

Страница 14: ...e if moisture levels are rising Refer to the Fluid sampling guidelines section in this manual If moisture levels increase determine leak point and repair Process or replace the fluid if water conent h...

Страница 15: ...arts the switchgear and high voltage transformer must be placed in a suitable test cage and all proper grounding procedures must be observed With the vacuum interrupters open manual operating handle s...

Страница 16: ...es Eaton com cooperpowerseries 2018 Eaton All Rights Reserved Printed in USA Publication No MN285006EN March 2018 KA20480375 Rev 09 Eaton is a registered trademark All trademarks are property of their...