manualshive.com logo in svg
background image

1

Type VFI, Fluid-insulated Switchgear 

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

   MN285006EN   March 2018

Product information

Introduction

Service Information MN285006EN

 provides installation 

instructions, operation information, maintenance 

procedures, and limited testing information for Eaton’s 

Cooper Power™ series Type VFI fluid-insulated underground 

distribution switchgear.
For in-depth testing information, refer to 

Service Information 

MN285001EN VFI Tester Operating Instructions

 for complete 

information regarding operation of the VFI tester and 

in-depth VFI underground distribution switchgear testing 

procedures.

Read this manual first

Read and understand the contents of this manual and follow 

all locally approved procedures and safety practices before 

installing or operating this equipment.

Additional information

These instructions do not claim to cover all details or 

variations in the equipment, procedures, or processes 

described, nor to provide directions for meeting every 

possible contingency during installation, operation, or 

maintenance. When additional information is desired to 

satisfy a problem not covered sufficiently for the user’s 

purpose, please contact your Eaton representative.

Acceptance and initial inspection

VFI switchgear is completely assembled, tested, and 

inspected at the factory. The switchgear is filled to the 

correct level with insulating fluid. It is in good condition 

when accepted by the freight carrier for shipment.
1.  Upon receipt, inspect the unit thoroughly for damage 

and loss of parts or fluid incurred during shipment. 

If damage or loss is discovered, file a claim with the 

carrier immediately.

2.  Check for fluid leakage and tighten any bolts that may 

have loosened during shipment.

Handling and storage

The switchgear should remain on its shipping pallet until it is 

installed. When handling the switchgear, always use a fork 

truck that has adequate lifting capacity and forks that extend 

the entire length of the pallet. Improper handling can cause 

damage to the switchgear. 
If the switchgear is to be stored for any appreciable time 

before installation, provide a clean, dry storage area. 

Be careful during handling and storage to minimize the 

possibility of mechanical damage. Do not stack other 

material on the switchgear.

Standards

Type VFI underground distribution switchgear products are 

designed and tested in accordance with IEEE Std C37.60™-

2003, IEEE Std C37.74™-2003, IEEE Std C.57.12.28™-2005, 

and IEEE Std 386™-2006 standards.

Quality standards

ISO 9001 Certified Quality Management System

Product description

Type VFI switchgear provides fault interruption and 

convenient load switching for 15, 25, and 35 kV underground 

systems. VFI switchgear is designed for outdoor mounting 

on a concrete pad. Power is fed to and from the switchgear 

from underground through openings in the pad.
Deadfront construction minimizes the high-voltage safety 

hazards for both the operator and the general public.
Type VFI switchgear employs mineral oil, Envirotemp™ 

FR3™, or Envirotemp™ E200™ as the insulating medium to 

provide a compact, low profile installation. 

 NOTICE

The use of Envirotemp™ FR3™ dielectric fluid is limited 

to a minimum operating temperature of 0 °C (32 °F) . 

Failure  to  comply  can  result  in  equipment  misoperation .                                                            

  

T374 .0

VFI switchgear can also be specified with a variety of 

control options to meet specific distribution system 

protection requirements

VFI switchgear operation

Type VFI switchgear utilizes vacuum interrupters to provide 

fault current interruption and load make/break switching 

capabilities. Hotstick-operable operating handles are located 

on the front plate of the unit. Vacuum fault interrupter 

operating mechanisms can be configured for either single- 

or ganged three-phase operation.
Current sensing transformers, located inside the switchgear 

tank, provide line current information to the control. When 

line current exceeds the minimum trip setting, the control 

initiates a signal which causes the vacuum fault interrupter 

to interrupt the circuit. Interruption may be single- or three-

phase, depending upon the configuration of the control and 

vacuum fault interrupter.

Содержание VFI

Страница 1: ...Type VFI Fluid insulated Switchgear Installation Operation and Maintenance Instructions COOPER POWER SERIES Underground Distribution Switchgear MN285006EN Effective March 2018 Supersedes December 2015...

Страница 2: ...PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS D...

Страница 3: ...binet construction 3 Standard features 3 Interrupter duty cycle 3 Switch test sequence 3 Finish 3 Nameplate 3 Operating handles 3 Weight 4 Special certifications 4 INSTALLATION PROCEDURE 4 OPERATION 5...

Страница 4: ...hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION...

Страница 5: ...e pallet Improper handling can cause damage to the switchgear If the switchgear is to be stored for any appreciable time before installation provide a clean dry storage area Be careful during handling...

Страница 6: ...llation Operation and Maintenance Instructions for operation information for the RVAC switch Vacuum fault interrupters Load and fault interruption takes place within sealed vacuum interrupters Figure...

Страница 7: ...37 74TM 2003 standard Padlocking provisions Provisions are included for padlocking the cabinet in order to prevent unauthorized door opening The cabinet must be locked at all times to prevent accident...

Страница 8: ...tances where a UL listing is required Figure 3 VFI switchgear operating handle three phase ganged operation Figure 4 VFI switchgear operating handles single phase operation Installation procedure WARN...

Страница 9: ...T223 2 5 Ground switchgear Switchgear must be adequately grounded Install a permanent low resistance ground connection to the switchgear tank Grounding provisions are provided near the bottom of the t...

Страница 10: ...aintenance Instructions for operation information for the RVAC switch Loadbreak switch In most configurations a Type RVAC loadbreak switch is integrated within the VFI switchgear The switch s push to...

Страница 11: ...ith sampler at the bottom of the tank If moisture is found in the tank refill with clean dry insulating fluid WARNING Hazardous voltage This equipment must be de energized and grounded prior to conduc...

Страница 12: ...ry T239 2 Use the following fluid sampling guidelines to prevent contamination and to safely extract fluid samples 1 De energize and ground the switchgear prior to sampling fluid 2 Where local governi...

Страница 13: ...from altering the moisture content of the sample Leave about one inch of air space in the container to account for thermal expansion 15 Retighten sampling valve to finger tight plus a 1 4 turn Reinsta...

Страница 14: ...e if moisture levels are rising Refer to the Fluid sampling guidelines section in this manual If moisture levels increase determine leak point and repair Process or replace the fluid if water conent h...

Страница 15: ...arts the switchgear and high voltage transformer must be placed in a suitable test cage and all proper grounding procedures must be observed With the vacuum interrupters open manual operating handle s...

Страница 16: ...es Eaton com cooperpowerseries 2018 Eaton All Rights Reserved Printed in USA Publication No MN285006EN March 2018 KA20480375 Rev 09 Eaton is a registered trademark All trademarks are property of their...

Отзывы: