Type VFI, Fluid-insulated Switchgear 

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

   MN285006EN   March 2018

WARNING

Hazardous voltage . Always use a hotstick when working 

with this equipment . Failure to do so could result in 

contact with high voltage, which will cause death or 

severe personal injury . 

G108A .0

The Type VFI switchgear is equipped with hotstick-operable 

handles that may be located on the tap- and/or source-side 

of the unit. The VFI switchgear can be configured for either 

single-phase or ganged three-phase operation (all three 

phases operated simultaneously with a single handle). 

The operating handle(s) (shown in 

Figure 3

 and 

Figure 4

provide convenient push-to-close and pull-to-open operation. 

The operating handle(s) may be padlocked in the open 

position. When configured for single-phase operation, each 

phase trips independently; however, the control may be 

configured to provide simultaneous tripping of all three 

phases.

Weight

The weight of the unit is shown on the nameplate. Make 

sure that lifting equipment used is rated sufficiently to safely 

handle the switchgear.

Special certifications

Units can be provided with a UL

®

 listing and labeling 

depending on the features specified. Please ensure 

appropriate labeling is provided prior to installation for 

instances where a UL

®

 listing is required.

Figure 3 .  VFI switchgear operating handle, three-phase 

ganged operation

Figure 4 .  VFI switchgear operating handles, single-

phase operation

Installation procedure

 WARNING

This equipment is not intended to protect human 

life . Follow all locally approved procedures and safety 

practices when installing or operating this equipment . 

Failure to comply can result in death, severe personal 

injury, and equipment damage . 

G102 .1

1. 

Check fluid level .

 Make sure the fluid in the switchgear 

tank is at the proper level by checking the fluid level 

indicator on the front plate(s). Some units have fluid 

level indicators on both source-side and tap-side front 

plates; both indicators should be at the proper level.

 WARNING

This equipment relies on dielectric fluid to provide 

electrical insulation between components . The dielectric 

strength and moisture content of the fluid must be 

checked on a regular basis, as part of the routine 

maintenance inspection, to ensure that it is at or 

above minimum dielectric requirements and below the 

maximum moisture content . Use of this equipment 

with dielectric fluid that does not meet requirements 

can result in internal flashovers that will damage the 

equipment and can result in death or serious injury .

 

G107 .3

2. 

Test fluid dielectric strength and moisture content .

 

If the switchgear has been stored for some time or 

is being relocated, perform these tests on the fluid in 

accordance with ASTM-approved testing procedures.

Содержание VFI

Страница 1: ...Type VFI Fluid insulated Switchgear Installation Operation and Maintenance Instructions COOPER POWER SERIES Underground Distribution Switchgear MN285006EN Effective March 2018 Supersedes December 2015...

Страница 2: ...PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS D...

Страница 3: ...binet construction 3 Standard features 3 Interrupter duty cycle 3 Switch test sequence 3 Finish 3 Nameplate 3 Operating handles 3 Weight 4 Special certifications 4 INSTALLATION PROCEDURE 4 OPERATION 5...

Страница 4: ...hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION...

Страница 5: ...e pallet Improper handling can cause damage to the switchgear If the switchgear is to be stored for any appreciable time before installation provide a clean dry storage area Be careful during handling...

Страница 6: ...llation Operation and Maintenance Instructions for operation information for the RVAC switch Vacuum fault interrupters Load and fault interruption takes place within sealed vacuum interrupters Figure...

Страница 7: ...37 74TM 2003 standard Padlocking provisions Provisions are included for padlocking the cabinet in order to prevent unauthorized door opening The cabinet must be locked at all times to prevent accident...

Страница 8: ...tances where a UL listing is required Figure 3 VFI switchgear operating handle three phase ganged operation Figure 4 VFI switchgear operating handles single phase operation Installation procedure WARN...

Страница 9: ...T223 2 5 Ground switchgear Switchgear must be adequately grounded Install a permanent low resistance ground connection to the switchgear tank Grounding provisions are provided near the bottom of the t...

Страница 10: ...aintenance Instructions for operation information for the RVAC switch Loadbreak switch In most configurations a Type RVAC loadbreak switch is integrated within the VFI switchgear The switch s push to...

Страница 11: ...ith sampler at the bottom of the tank If moisture is found in the tank refill with clean dry insulating fluid WARNING Hazardous voltage This equipment must be de energized and grounded prior to conduc...

Страница 12: ...ry T239 2 Use the following fluid sampling guidelines to prevent contamination and to safely extract fluid samples 1 De energize and ground the switchgear prior to sampling fluid 2 Where local governi...

Страница 13: ...from altering the moisture content of the sample Leave about one inch of air space in the container to account for thermal expansion 15 Retighten sampling valve to finger tight plus a 1 4 turn Reinsta...

Страница 14: ...e if moisture levels are rising Refer to the Fluid sampling guidelines section in this manual If moisture levels increase determine leak point and repair Process or replace the fluid if water conent h...

Страница 15: ...arts the switchgear and high voltage transformer must be placed in a suitable test cage and all proper grounding procedures must be observed With the vacuum interrupters open manual operating handle s...

Страница 16: ...es Eaton com cooperpowerseries 2018 Eaton All Rights Reserved Printed in USA Publication No MN285006EN March 2018 KA20480375 Rev 09 Eaton is a registered trademark All trademarks are property of their...

Отзывы: