54
Appendix
9
V. USER INTERFACE
1. 7 in. color touchscreen high resolution interface
2. Allows user and service personnel to adjust settings mentioned throughout this document
a. User supply air temp setting range: 64~99°F (18~37°C)
3. Features home screen with status indicators
4. Features 3 password protected service levels: 1) User, 2) Service, and 3) Factory settings
5. Features temperature and pressure graphing/plotting screen for easy visual tracking of system performance and
behavior
6. Features dedicated alarm list and log
7. Features a read-only, real-time data parameter screen
8. Firmware upgradeable in field
W. CONTROLLER
1. Supports all commands locally and remotely
2. Governs the speed of the compressor and fans
3. Utilizes the return air temperature and humidity sensor, supply air temperature sensor, along with other sensors,
to control system behavior
4. Firmware upgradeable in field
X. FILTERS
1. Qty. 2, extending full height of cabinet
2. Efficiency rating: G4
3. Replaceable and easy to service from the rear of the cabinet
4. Size/Dimensions: 33 x 8.5 in. (84 x 22 cm)
Y. LOW TEMPERATURE KIT (SRCOOLDXRWLTKIT, OPTIONAL)
1. Optional accessory
2. Comes with all necessary components preassembled, includes a heater mounted to the receiver tank
3. Powered from In-Row (indoor unit)
4. Necessary for outdoor ambient temperature ranging from -4°F (-20°C) to -40°F (-40°C)
Z. PROTECTION METHODS
1. Oil separator
a. Ensures proper oil return to the compressor for maximum reliability
2. Tip-N-Tell
a. Determines whether the product has been potentially damaged by tracking the angle of the package
b. Indicator is visible on the outside package
3. ISTA testing
a. ISTA-1B tested: shock, vibration, and drop
AA. SPARE PARTS
1. Full range of spare parts to allow full servicing in the field