47
Appendix
2
A. PERFORMANCE
SRCOOLDXRW12
SRCOOLDXRW25
Working conditions
Rated cooling capacity (see Section CC
for additional detail)
12.8 kW (43 kBTU)
25.8 kW (88 kBTU)
Rated indoor return air temperature and
RH 24%.*
98.6°F (37°C)
98.6°F (37°C)
Rated outdoor temperature
95°F (35°C)
95°F (35°C)
Energy Efficiency Rating (EER) W/W
3.8
3.9
Approx minimum cooling capacity
(continuous)
4 kW
8 kW
Maximum cooling capacity**
13.2 kw (45 kBTU)
27.3 kw (93.2 kBTU)
Maximum outdoor operating
temperature
up to 113°F (45°C)
up to 113°F (45°C)
Minimum outdoor operating
temperature without low temp kit
installed
down to -4°F (–20°C)
down to -4°F (–20°C)
Minimum outdoor operating
temperature with low temp kit
(SRCOOLDXRWLTKIT) installed
down to -40°F (–40°C)
down to -40°F (–40°C)
Acceptable humidity operating range
(indoor)
5 to 80% RH
5 to 80% RH
Maximum operational altitude (see
chart in Section DD for altitude
correction factors)
up to 13,000 ft. (4,000 m)
up to 13,000 ft. (4,000 m)
* For maximum cooling capacity and RH operating scenarios, see chart in Section CC.
** With indoor return air temperature of 104°F (40°C) and 20% RH (see Section CC for additional detail).
B. COMPLIANCE APPROVALS
1. ANSI/UL 60335-1 and ANSI/UL 60335-2-40
2. CAN/CSA-C22.2 No. 60335-2-40-2017
3. FCC/ICES Compliant; CLASS A; 47 CFR FCC PART 15 SUBPART B; ICES-003 Issue 7
4. NOM
5. RoHS
C. CABINET (IN-ROW)
1. 300 mm wide for maximum cooling capacity with minimal floorspace consumption
2. Horizontal airflow pass-thru: no raised floor required
3. Matching cabinet depth and height with standard IT rack
4. Rigid formed steel cabinet
5. Removable side panels both left and right for easy servicing
6. Front and rear doors for easy servicing
7. Color code RAL 9005