51
Appendix
6
K. STABILIZERS
1. Casters
a. Qty. 4 all four corners
b. Full swivel for each
c. Allows cabinet to be maneuvered from room to room and into position without the need for special lifting
equipment
2. Leveling feet
a. Qty. 4 adjustable leveling feet all four corners
b. Stabilizes cabinet into place
3. Baying brackets
a. Included with package
b. Supports both flush and protruded/staggered installation
L. EXPANSION VALVE AND FILTER DRIER
1. Electronic Expansion Valve (EEV)
a. Comes standard with electronic type, for better stability and control over thermal type
b. Increased cooling precision
c. Improved energy efficiency
d. Improved turndown ratio (improves minimum capacity)
2. Filter drier
a. Included in refrigeration circuit to catch particulates and remove moisture inside the piping
M. PIPING AND ELECTRICAL CONNECTIONS
1. Top or bottom entry: piping/electrical can be routed from top or bottom into the In-Row cooler; no modifications
required
2. Designated ports both top and bottom with grommets to protect against vibration
3. Strain relief provided for electrical terminal connections
N. POWER INPUT
SRCOOLDXRW12
SRCOOLDXRW25
Power input (In-Row cooler)
Rated Input Power, Indoor Unit
208V, 3ph, 60 Hz
208V, 3ph, 60 Hz
Voltage input range
200-240V
200-240V
Voltage input tolerance
±10%
±10%
Frequency range
48-62 Hz
48-62 Hz
Connection type
Hardwired
Hardwired
MCA (Minimum Current Ampacity)
19A
33A
MOP (Maximum Overcurrent Protection)
25A
50A
In-rush current
Soft-start
Soft-start
Strain Relief
Included
Included
Power input (condenser)
Input Power from Indoor Cooling Unit
208V, 1ph, 60 Hz
208V, 3ph, 60 Hz
Voltage input range
200-240V
200-240V
Voltage input tolerance
±10%
±10%
Frequency range
48-62 Hz
48-62 Hz
Connection type
Hardwired from
In-Row (Indoor Unit)
Hardwired from
In-Row (Indoor Unit)
Signal wire (from In-Row)
20 AWG
20 AWG
FLA
2.9A
3.2A