13
3.4 Leveling the POD Unit
WARNING: Level the enclosure before attempting to install equipment. The casters are not designed to
provide long-term support for the enclosure. Use the levelers to provide long-term support. Install the POD
unit in a structurally sound area with a level floor that can bear the weight of the enclosures, all
equipment that will be installed in the enclosures and any other enclosures and/or equipment that will be
installed nearby.
3. Configuration
FLOOR
1
Once the POD unit has been
moved to the installation location,
ensure the entire unit is level for
proper condensate drainage. Use
a carpenter’s level to check the
slope of the floor. If the floor
slopes more than 1%, choose an
alternate installation site.
1
1
2
2
3
3
1
1
2
Use an 18 mm open-end wrench
to lower each leveler
1
until it
touches the floor (there are 4
levelers: 2 at the front and 2 at
the rear). Make sure each leveler
contacts the floor firmly.
Note:
Lower a leveler by turning it
clockwise; raise a leveler by turning it
counter-clockwise.
3
After lowering each leveler, use
the carpenter’s level to confirm
that the POD unit is level in all
directions. Adjust the levelers as
required until the enclosures/
POD unit is level.