Installation
2
S611 Soft Starter
MN03901003E—January 2012 www.eaton.com
CT Polarity Identification
CT Location
Line and Load Power Wiring
Notes
Additional lug selection may be found in
Appendix D
of the User Manual, Publication No. MN03902011E.
Each lug kit consists of three lugs. Two kits are required for both line and load connections.
Wire size based on 125% of UL 508 Table 43.2.
Short-Circuit Rating
Suitable for use on a circuit capable of delivering not more than 100,000 rms
symmetrical amperes, 600 volts maximum when protected by Class RK5 fuses or a
circuit breaker having an interrupting rating not less than 65,000 rms symmetrical
amperes, 480 volts maximum.
Current
Rating
Conductor
Size
Number of
Conductors
Mechanical Lug—
Ilsco Part Number
Torque
lb-in
Mechanical
Lug Range
Soft Starter
Catalog Number
Mechanical Lug—
Eaton Catalog Number
52A
6 AWG
1
TA-2/0
120
14 AWG–2/0
S611A052XXX
S611-LUG-MO1
65A
4 AWG
1
TA-2/0
120
14 AWG–2/0
S611A065XXX
S611-LUG-MO1
77A
3 AWG
1
TA-2/0
120
14 AWG–2/0
S611A072XXX
S611-LUG-MO1
99A
1/0 AWG
1
TA-300
275
14 AWG–2/0
S611B099XXX
S611-LUG-MO2
125A
2/0 AWG
1
TA-300
275
2 AWG–600 kcmil
S611B125XXX
S611-LUG-MO2
156A
3/0 AWG
1
TA-600
500
2 AWG–600 kcmil
S611C156XXX
S611-LUG-MO3
180A
4/0 AWG
1
TA-600
500
2 AWG–600 kcmil
S611C180XXX
S611-LUG-MO3
242A
350 kcmil
1
TA-600
500
2 AWG–600 kcmil
S611D242XXX
S611-LUG-MO3
302A
3/0 AWG
2
AU-600-2NS
500
2 AWG–600 kcmil
S611E302XXX
S611-LUG-MO4
361A
4/0 AWG
2
AU-600-2NS
500
2 AWG–600 kcmil
S611E361XXX
S611-LUG-MO4
414A
300 kcmil
2
AU-600-2NS
500
300–800 kcmil
S611F414XXX
S611-LUG-MO4