Installation

2

S611 Soft Starter

    MN03901003E—January 2012    www.eaton.com

CT Polarity Identification

CT Location

Line and Load Power Wiring 

Notes

Additional lug selection may be found in 

Appendix D

 of the User Manual, Publication No. MN03902011E.

Each lug kit consists of three lugs. Two kits are required for both line and load connections. 

Wire size based on 125% of UL 508 Table 43.2.

Short-Circuit Rating

Suitable for use on a circuit capable of delivering not more than 100,000 rms 
symmetrical amperes, 600 volts maximum when protected by Class RK5 fuses or a 
circuit breaker having an interrupting rating not less than 65,000 rms symmetrical 
amperes, 480 volts maximum.

Current 
Rating

Conductor 
Size 

Number of 
Conductors

Mechanical Lug—
Ilsco Part Number

Torque
lb-in

Mechanical 
Lug Range

Soft Starter 
Catalog Number

Mechanical Lug—
Eaton Catalog Number

52A

6 AWG

1

TA-2/0

120

14 AWG–2/0

S611A052XXX

S611-LUG-MO1

65A

4 AWG 

1

TA-2/0

120

14 AWG–2/0

S611A065XXX

S611-LUG-MO1

77A

3 AWG

1

TA-2/0

120

14 AWG–2/0

S611A072XXX

S611-LUG-MO1

99A

1/0 AWG

1

TA-300

275

14 AWG–2/0

S611B099XXX

S611-LUG-MO2

125A

2/0 AWG

1

TA-300

275

2 AWG–600 kcmil

S611B125XXX

S611-LUG-MO2

156A

3/0 AWG

1

TA-600

500

2 AWG–600 kcmil

S611C156XXX

S611-LUG-MO3

180A

4/0 AWG

1

TA-600

500

2 AWG–600 kcmil

S611C180XXX

S611-LUG-MO3

242A

350 kcmil

1

TA-600

500

2 AWG–600 kcmil

S611D242XXX

S611-LUG-MO3

302A

3/0 AWG

2

AU-600-2NS

500

2 AWG–600 kcmil

S611E302XXX

S611-LUG-MO4

361A

4/0 AWG

2

AU-600-2NS

500

2 AWG–600 kcmil

S611E361XXX

S611-LUG-MO4

414A

300 kcmil

2

AU-600-2NS

500

300–800 kcmil

S611F414XXX

S611-LUG-MO4

www.comoso.com

Содержание S611

Страница 1: ...S611 Soft Starter Quick Start Installation Guide Effective January 2012 Supersedes June 2011 www comoso com...

Страница 2: ...www comoso com...

Страница 3: ...MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECO...

Страница 4: ...E 386 2273 8 00 a m 6 00 p m EST FAX 800 752 8602 After Hours Emergency 800 543 7038 6 00 p m 8 00 a m EST If you are in the U S or Canada and have OI or PLC questions you can take advantage of our to...

Страница 5: ...tarter Do not attempt to lift the soft starter by the cover only Lug Installation Install the lugs below the bus bar to assure anti rotation Refer to figure Lug and Bolt Torque Support on this page Po...

Страница 6: ...ze Number of Conductors Mechanical Lug Ilsco Part Number Torque lb in Mechanical Lug Range Soft Starter Catalog Number Mechanical Lug Eaton Catalog Number 52A 6 AWG 1 TA 2 0 120 14 AWG 2 0 S611A052XXX...

Страница 7: ...ting Hole Dimensions Approximate Dimensions in mm Inches Frames A through D Frames E and F 70 0 2 76 464 7 18 30 110 0 4 33 10 0 0 39 70 0 2 76 80 0 3 15 90 0 3 54 80 0 3 15 155 0 6 10 562 0 22 13 10...

Страница 8: ...ive L Permissive N Start L Start N Reset L Reset Reset E Stop Maintained Momentary Comms Adapter Comms Modbus TB4 DeviceNet Modbus PROFIBUS TB5 Module Ground 24V D0 D1 Common N Tap Neutral L Tap Line...

Страница 9: ...on Operation LED list Navigates through display parameter list in Monitor mode Edit Save Selects Saves parameter values in Protection Operation modes Selects Advanced Con g Menu parameters Selects Sav...

Страница 10: ...rt time elapses Verify that the motor is not overloaded After suitable performance has been achieved with either method determine the starting time to bypass and set Soft Start Time at 1 25 times this...

Страница 11: ...45 67 Default value 36 60 33 57 Wye delta equivalent 27 52 19 44 Minimum for current limit 14 37 9 30 1 10 Minimum Application t Start t Stop u Start Breakaway Torque Remarks Crusher empty at start 20...

Страница 12: ...ch network controller verify that the unit is recognized by the system controller Comms Port B adapter module failed or disconnected 15 Power Pole Over Temperature SCR temperature is above limits Oper...

Страница 13: ...Incoming AC line voltage below trip threshold Incorrect mains supply voltage Connect to correct supply voltage Verify that mains voltage is within acceptable values Verify Motor Rated Voltage in the...

Страница 14: ...imbalance problem with mains Increase the Voltage Fault Imbalance parameters Disable the fault if the other issues cannot be resolved 33 Jam Soft starter in bypass Motor below rated RPM and or current...

Страница 15: ...www comoso com...

Страница 16: ...liable efficient and safe power is available when it s needed most With unparalleled knowledge of electrical power management across industries experts at Eaton deliver customized integrated solutions...

Отзывы: