Troubleshooting

8

S611 Soft Starter

    MN03901003E—January 2012    www.eaton.com

Troubleshooting

S611 Fault Codes

Code

Fault

Condition

Solution

3

Watchdog

Firmware fault

5

Internal Memory

Internal FRam memory error

Component failure on printed circuit board

Contact EatonCare for service

6

User Interface Communications 
Failure

Communications to UI have been 
interrupted

Possible hardware failure

Firmware is not communicating internally

Cycle 120 Vac control voltage power to attempt to 
clear problem

7

Internal Program Memory

Corrupted firmware or memory

Flash CRC

Cycle 120 Vac control power to the S611

Contact EatonCare for service

8

Voltage Zero Cross Lost

Mains voltage lost

Phase L1 or L3 lost

Load disconnected

Restore mains or lost phases

Verify that the load is connected and any disconnect 
devices are properly engaged

Contact EatonCare for service

9

Communications Loss Port A

Communications to a remote network 
controller was lost during run cycle

Device disconnected

Connection lost

Reattach network controller, verify that the unit is 
recognized by the system controller

10

Communications Loss Port B

Communications to a remote network 
controller was lost during run cycle

Device disconnected

Connection lost

Reattach network controller, verify that the unit is 
recognized by the system controller

Comms Port B adapter module failed or disconnected

15

Power Pole Over Temperature

SCR temperature is above limits

Operating environment above specified 
maximum temperature

Ventilation holes blocked

Fans are not operational

Starts/hour exceed specifications

Sensor failure on power pole

Bypass contactor(s) failed to close

Ventilate to specified maximum temperatures

Clear obstructions

Verify fans are operational

Verify system is not exceeding the specified 
maximum starts per hour

Verify bypass contacts are closing at the end of ramp 
time

Reduce excessive cabinet temperature

16

Bypass Failure

Internal bypass contactor(s) not closed 
and/or electrically sealed after ramp time

Contactor(s) opened in bypass

Verify all bypass contactor(s) close (audible noise)

Verify all bypass contactor(s) not opening during run 
cycle due to excessive vibration and/or shock
Reduce levels of vibration and/or shock

Verify control power and wire size meet 
specifications

Verify that the control power supply meets the 
120 Vac voltage and current requirements of the 

IT.

 soft starter

17

SCR Not Firing

SCR is not conducting when gated 
Incoming phase lost

Special application—undersized or high 
impedance motor

Load disconnected

SCR failure

Re-apply lost phase

Review S611 application

Circuitry damaged by megger testing

Contact EatonCare for service

www.comoso.com

Содержание S611

Страница 1: ...S611 Soft Starter Quick Start Installation Guide Effective January 2012 Supersedes June 2011 www comoso com...

Страница 2: ...www comoso com...

Страница 3: ...MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECO...

Страница 4: ...E 386 2273 8 00 a m 6 00 p m EST FAX 800 752 8602 After Hours Emergency 800 543 7038 6 00 p m 8 00 a m EST If you are in the U S or Canada and have OI or PLC questions you can take advantage of our to...

Страница 5: ...tarter Do not attempt to lift the soft starter by the cover only Lug Installation Install the lugs below the bus bar to assure anti rotation Refer to figure Lug and Bolt Torque Support on this page Po...

Страница 6: ...ze Number of Conductors Mechanical Lug Ilsco Part Number Torque lb in Mechanical Lug Range Soft Starter Catalog Number Mechanical Lug Eaton Catalog Number 52A 6 AWG 1 TA 2 0 120 14 AWG 2 0 S611A052XXX...

Страница 7: ...ting Hole Dimensions Approximate Dimensions in mm Inches Frames A through D Frames E and F 70 0 2 76 464 7 18 30 110 0 4 33 10 0 0 39 70 0 2 76 80 0 3 15 90 0 3 54 80 0 3 15 155 0 6 10 562 0 22 13 10...

Страница 8: ...ive L Permissive N Start L Start N Reset L Reset Reset E Stop Maintained Momentary Comms Adapter Comms Modbus TB4 DeviceNet Modbus PROFIBUS TB5 Module Ground 24V D0 D1 Common N Tap Neutral L Tap Line...

Страница 9: ...on Operation LED list Navigates through display parameter list in Monitor mode Edit Save Selects Saves parameter values in Protection Operation modes Selects Advanced Con g Menu parameters Selects Sav...

Страница 10: ...rt time elapses Verify that the motor is not overloaded After suitable performance has been achieved with either method determine the starting time to bypass and set Soft Start Time at 1 25 times this...

Страница 11: ...45 67 Default value 36 60 33 57 Wye delta equivalent 27 52 19 44 Minimum for current limit 14 37 9 30 1 10 Minimum Application t Start t Stop u Start Breakaway Torque Remarks Crusher empty at start 20...

Страница 12: ...ch network controller verify that the unit is recognized by the system controller Comms Port B adapter module failed or disconnected 15 Power Pole Over Temperature SCR temperature is above limits Oper...

Страница 13: ...Incoming AC line voltage below trip threshold Incorrect mains supply voltage Connect to correct supply voltage Verify that mains voltage is within acceptable values Verify Motor Rated Voltage in the...

Страница 14: ...imbalance problem with mains Increase the Voltage Fault Imbalance parameters Disable the fault if the other issues cannot be resolved 33 Jam Soft starter in bypass Motor below rated RPM and or current...

Страница 15: ...www comoso com...

Страница 16: ...liable efficient and safe power is available when it s needed most With unparalleled knowledge of electrical power management across industries experts at Eaton deliver customized integrated solutions...

Отзывы: