Setup and Starting—Initial Configuration
6
S611 Soft Starter
MN03901003E—January 2012 www.eaton.com
Setup and Starting—Initial Configuration
1.
The S611 Operation and Protection parameters may be
edited when 120 Vac control power is applied to 120 Vac
supply (TB1). Mains power is not required to edit and
save Operation and/or Protection parameters.
2.
If any 120 Vac power source other than the normal system
control power source is used to power the control circuit to
edit parameters, connections must be made in compliance
with all local, state, and national electrical codes.
3.
To setup the S611 Operating parameters (Operation
mode), perform the following steps:
a.
Enter motor FLA.
b.
Enter motor rated voltage.
c.
Select start method if required (default = voltage
ramp, or pump start).
d.
Enter Start time from table on
Page 7
(default =
20 seconds).
e.
Enter initial torque from table on
Page 7
(default =
45%).
f.
Enter Stop time, Kick Start time, and Kick Start
torque if desired (default = 0).
4.
Application Notes
Adjust
Initial Torque
for smooth start, motor rotation
should begin within 2 seconds.
If Stall Faults occur at the end of the ramp time, increase
Initial Torque, Kick Start Torque and Time and/or Soft
Start Time
to achieve bypass before the Soft Start time
elapses. Verify that the motor is not overloaded.
After suitable performance has been achieved with either
method, determine the starting time to bypass and set
Soft Start Time
at 1.25 times this time. For example, if it
takes 10 seconds to accelerate the motor and go into
bypass, set the
Soft Start Time
for 12.5 seconds.
5.
In the Protection Mode, set the Protection parameters
to the desired values. Refer to table on
Page 7
.
6.
For optional advanced configuration parameters refer to
the user manual.
Operating Parameters
Notes
For the device with pump option, the default value is 2 for pump start.
Operating Parameter
Units
Min
Max
Default
Notes
Motor FLA
Amps
Motor FLA parameter must be set to
motor nameplate FLA to achieve
proper overload protection
Frame Size A–52
26
52
26
Frame Size A–65
32.5
65
32.5
Frame Size A–77
38.5
77
38.5
Frame Size B–99
48
99
48
Frame Size B–125
62.5
125
62.5
Frame Size C–156
78
156
78
Frame Size C–180
90
180
90
Frame Size D–242
120
242
120
Frame Size E–302
151
302
151
Frame Size E–361
180.5
361
180.5
Frame Size F–414
207
414
207
Motor rated voltage
Volts
200
600
480
—
Start method
—
0
2
0
0
= Voltage ramp
1
= Current limit
2
= Pump start (option)
Start time
Seconds
0.5
180
20
—
Initial torque
%
0
100
45
—
Stop time
Seconds
0
60
0
—
Kick start time
Seconds
0
2
0
—
Kick start torque
%
0
100
0
—
Auto reset mode
—
0
1
0
0
= Manual
1
= Auto
Advanced config
—
—
—
—
Refer to User Manual, Publication No.
MN03902011E