Troubleshooting

10

S611 Soft Starter

    MN03901003E—January 2012    www.eaton.com

S611 Fault Codes, continued

Note:

All mains and control power connections must be completed and voltage applied prior 
to a START command. Failure to make all connections will result in one or more faults.

All isolation and/or reversing contactors must be staged prior to any START commands. 
Manipulating contactors after the START command will result in one or more faults.

Code

Fault

Condition

Solution

29

Current Unbalance

The current imbalance of the incoming 
phases exceeds the trip threshold

Correct imbalance problem with mains

Increase the 

Current Imbalance

 parameters

Disable the fault if the other issues cannot be 
resolved

30

Current Phase Loss

Incoming phase disconnected

Open fuse or breaker

Phase imbalance exceeds specifications 
or trip parameter

Severe voltage phase imbalance

Repair broken connection

Replace fuse

Inspect system for phase imbalance conditions

31

Voltage Phase Imbalance 

The voltage imbalance of the incoming 
phases exceeds the trip threshold

Correct imbalance problem with mains

Increase the 

Voltage Fault Imbalance

 parameters

Disable the fault if the other issues cannot be resolved

33

Jam

Soft starter in bypass: Motor below rated 
RPM and/or current exceeds 3 x motor 
FLA

Remove obstruction

Verify proper FLA setting in Operation mode

Jam fault can be disabled if trips occur during normal 
operation (Overcurrent fault will provide protection at 
a higher current threshold of 4 x catalog FLA)

34

Contactor Overcurrent

Only active in bypass if the jam fault is 
disabled

Current exceeds the fault threshold of 
4 x catalog FLA

Remove obstruction in motor drive train

Verify S611 is properly sized for the application

35

Missing Temp Sensor

Temperature sensor failure

Internal connection failure

Internal hardware failure (sensor and/or cable)

Note:

 Disabling this feature (

Temp Sense 

fault in 

Protection

 menu) will remove protection from 

excessive temperature exposure (not recommended)

Not field repairable, contact Eaton Support

*

Cannot RESET fault

Fault condition still exists

Soft starter has not received RESET 
signal

Troubleshoot fault and correct defective condition

Attempt alternate methods of RESET

NC

No communication

Firmware not programmed, firmware 
corrupted

Contact EatonCare for service

www.comoso.com

Содержание S611

Страница 1: ...S611 Soft Starter Quick Start Installation Guide Effective January 2012 Supersedes June 2011 www comoso com...

Страница 2: ...www comoso com...

Страница 3: ...MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECO...

Страница 4: ...E 386 2273 8 00 a m 6 00 p m EST FAX 800 752 8602 After Hours Emergency 800 543 7038 6 00 p m 8 00 a m EST If you are in the U S or Canada and have OI or PLC questions you can take advantage of our to...

Страница 5: ...tarter Do not attempt to lift the soft starter by the cover only Lug Installation Install the lugs below the bus bar to assure anti rotation Refer to figure Lug and Bolt Torque Support on this page Po...

Страница 6: ...ze Number of Conductors Mechanical Lug Ilsco Part Number Torque lb in Mechanical Lug Range Soft Starter Catalog Number Mechanical Lug Eaton Catalog Number 52A 6 AWG 1 TA 2 0 120 14 AWG 2 0 S611A052XXX...

Страница 7: ...ting Hole Dimensions Approximate Dimensions in mm Inches Frames A through D Frames E and F 70 0 2 76 464 7 18 30 110 0 4 33 10 0 0 39 70 0 2 76 80 0 3 15 90 0 3 54 80 0 3 15 155 0 6 10 562 0 22 13 10...

Страница 8: ...ive L Permissive N Start L Start N Reset L Reset Reset E Stop Maintained Momentary Comms Adapter Comms Modbus TB4 DeviceNet Modbus PROFIBUS TB5 Module Ground 24V D0 D1 Common N Tap Neutral L Tap Line...

Страница 9: ...on Operation LED list Navigates through display parameter list in Monitor mode Edit Save Selects Saves parameter values in Protection Operation modes Selects Advanced Con g Menu parameters Selects Sav...

Страница 10: ...rt time elapses Verify that the motor is not overloaded After suitable performance has been achieved with either method determine the starting time to bypass and set Soft Start Time at 1 25 times this...

Страница 11: ...45 67 Default value 36 60 33 57 Wye delta equivalent 27 52 19 44 Minimum for current limit 14 37 9 30 1 10 Minimum Application t Start t Stop u Start Breakaway Torque Remarks Crusher empty at start 20...

Страница 12: ...ch network controller verify that the unit is recognized by the system controller Comms Port B adapter module failed or disconnected 15 Power Pole Over Temperature SCR temperature is above limits Oper...

Страница 13: ...Incoming AC line voltage below trip threshold Incorrect mains supply voltage Connect to correct supply voltage Verify that mains voltage is within acceptable values Verify Motor Rated Voltage in the...

Страница 14: ...imbalance problem with mains Increase the Voltage Fault Imbalance parameters Disable the fault if the other issues cannot be resolved 33 Jam Soft starter in bypass Motor below rated RPM and or current...

Страница 15: ...www comoso com...

Страница 16: ...liable efficient and safe power is available when it s needed most With unparalleled knowledge of electrical power management across industries experts at Eaton deliver customized integrated solutions...

Отзывы: