Troubleshooting

S611 Soft Starter

    MN03901003E—January 2012    www.eaton.com

9

S611 Fault Codes, continued

Note

Shorted SCRs are the most common mode of SCR failure. With power completely removed from the unit, measure the resistance of each pole, line to load. 
If the resistance is near zero (less than 5 ohms), it is most likely that the SCR is shorted. Resistance of a serviceable SCR is approximately 10k ohms. 
Resistance typically moves to a lower value as the SCR ages. This feature may be disabled (not recommended).

Code

Fault

Condition

Solution

18

Shorted SCR 

SCR is shorted

Internal bypass contactor welded shut

No load on the SCRs when START 
command is issued

Test resistance of each phase

Contact EatonCare for service

19

Instantaneous Overcurrent

Excessive starting current

Excessive load

Reduce starting load

Increase soft starter capacity (be sure model ratings 
can handle current demands)

20

Overload 

Motor overloaded for an extended 
period of time

Thermal memory is over 100%

Reduce the motor’s load

Verify the 

Overld Trip FLA

 and/or 

Ovrld Trip Class

 for 

proper adjustment

Note:

 Exceeding nameplate ratings will shorten 

equipment life

Fault during motor start: Verify system is not 
exceeding the specified maximum starts per hour

Increase the initial torque and/or reduce ramp time 
to bring the motor up to speed faster

Increase Trip Class setting (5–30 maximum) and/or 
reduce ramp time setting

21

Mains AC Voltage Loss

Fuses or breaker open

Disconnect open

Replace fuses, close disconnect, or reset breaker

22

Under Voltage

Incoming AC line voltage below trip 
threshold

Incorrect mains supply voltage

Connect to correct supply voltage

Verify that mains voltage is within acceptable values

Verify

 Motor Rated Voltage

 in the 

Operation 

mode is 

set to the correct value

23

Over Voltage

Incoming AC line voltage above trip 
threshold

Incorrect mains supply voltage

Connect to correct supply voltage

Verify

 Motor Rated Voltage

 in the 

Operation 

mode is 

set to correct value

24

Phase Reversal

Incoming line phase rotation sequence 
opposite of device setting

Single-phase missing and/or open fuse 
or breaker

Set 

Phase Sequence

 to match incoming sequence OR

Exchange two incoming mains phases

Verify that all circuit breakers are closed or fuses are 
serviceable

25

Start Stall

Motor not at rated RPM at end of start 
ramp time and/or current is in excess of 
trip threshold

Bypass contactors not closed at the end 
of the start time (start current low/ramp 
time short)

Lengthen 

Soft Start Time

 and/or increase 

Initial 

Torque

 in the 

Operations 

mode

Increase trip threshold

Loads that are heavily loaded (high inertia) during a 
start such as fans will often need an initial torque 
setting much greater than the factory default

Set 

Kick Start

 parameters

27

SCR Overcurrent

Excessive SCR current during the start 
ramp

Only active when Stall Fault is disabled

Increase 

Soft Start Time

 and/or 

Initial Torque

 

parameters in 

Operation 

mode

Reduce starting load

Verify S611 is properly rated for current

28

Under Load

Loss of motor load

Trip threshold set too high

Excessive current fluctuation during 
operation

Inspect for failed motor coupling or pump cavitation

Reduce trip threshold

Increase trip delay time to ride through transient load 
changes

www.comoso.com

Содержание S611

Страница 1: ...S611 Soft Starter Quick Start Installation Guide Effective January 2012 Supersedes June 2011 www comoso com...

Страница 2: ...www comoso com...

Страница 3: ...MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECO...

Страница 4: ...E 386 2273 8 00 a m 6 00 p m EST FAX 800 752 8602 After Hours Emergency 800 543 7038 6 00 p m 8 00 a m EST If you are in the U S or Canada and have OI or PLC questions you can take advantage of our to...

Страница 5: ...tarter Do not attempt to lift the soft starter by the cover only Lug Installation Install the lugs below the bus bar to assure anti rotation Refer to figure Lug and Bolt Torque Support on this page Po...

Страница 6: ...ze Number of Conductors Mechanical Lug Ilsco Part Number Torque lb in Mechanical Lug Range Soft Starter Catalog Number Mechanical Lug Eaton Catalog Number 52A 6 AWG 1 TA 2 0 120 14 AWG 2 0 S611A052XXX...

Страница 7: ...ting Hole Dimensions Approximate Dimensions in mm Inches Frames A through D Frames E and F 70 0 2 76 464 7 18 30 110 0 4 33 10 0 0 39 70 0 2 76 80 0 3 15 90 0 3 54 80 0 3 15 155 0 6 10 562 0 22 13 10...

Страница 8: ...ive L Permissive N Start L Start N Reset L Reset Reset E Stop Maintained Momentary Comms Adapter Comms Modbus TB4 DeviceNet Modbus PROFIBUS TB5 Module Ground 24V D0 D1 Common N Tap Neutral L Tap Line...

Страница 9: ...on Operation LED list Navigates through display parameter list in Monitor mode Edit Save Selects Saves parameter values in Protection Operation modes Selects Advanced Con g Menu parameters Selects Sav...

Страница 10: ...rt time elapses Verify that the motor is not overloaded After suitable performance has been achieved with either method determine the starting time to bypass and set Soft Start Time at 1 25 times this...

Страница 11: ...45 67 Default value 36 60 33 57 Wye delta equivalent 27 52 19 44 Minimum for current limit 14 37 9 30 1 10 Minimum Application t Start t Stop u Start Breakaway Torque Remarks Crusher empty at start 20...

Страница 12: ...ch network controller verify that the unit is recognized by the system controller Comms Port B adapter module failed or disconnected 15 Power Pole Over Temperature SCR temperature is above limits Oper...

Страница 13: ...Incoming AC line voltage below trip threshold Incorrect mains supply voltage Connect to correct supply voltage Verify that mains voltage is within acceptable values Verify Motor Rated Voltage in the...

Страница 14: ...imbalance problem with mains Increase the Voltage Fault Imbalance parameters Disable the fault if the other issues cannot be resolved 33 Jam Soft starter in bypass Motor below rated RPM and or current...

Страница 15: ...www comoso com...

Страница 16: ...liable efficient and safe power is available when it s needed most With unparalleled knowledge of electrical power management across industries experts at Eaton deliver customized integrated solutions...

Отзывы: