34
PT UNIT USER MANUAL
APRIL 2023 www.eaton.com.cn
Appendix A - Modbus Communication Port Setting
Register
Bit Field
Mask
Field
Setpoint Name
R/W
Format
Value Definition
403019
7-0
0x00FF
Ground Pickup (I
g
)
R/W
Unsigned
0 = OFF
20~100, step is 1 (indicating 0.20I
n
~1.00I
n
)
403020
7-0
0x00FF
Ground Time (t
g
)
R/W
Unsigned
10~50, step is 1 (indicating 0.10~0.50 second)
403021
0
0x0001
Ground Fault Thermal
memory
R/W
Encoded
0 = Disabled
1 = Enabled
403022
6-0
0x007F
Neutral Protection Ratio
R/W
Unsigned
0 = 0%
60 = 60%
100 = 100%
403023
6-0
0x007F
High Load Alarm 2
R/W
Unsigned
0: OFF
50<=High load alarm 1< High load alarm 2<=120 (%)
403024
6-0
0x007F
Ground Fault Early Warning R/W
Unsigned
50~100, step is 1 (indicating 50%~100%)
403025
6-0
0x007F
Thermal Memory Alarm
Threshold Setting
R/W
Unsigned
50~100, step is 1 (indicating 50%~100%)
Table A5. Setpoints Group 1: Protection Group. (continued)