32
PT UNIT USER MANUAL
APRIL 2023 www.eaton.com.cn
Table A4. Setpoints Group 0: System Group (continued)
Register
Bit
Field
Mask
Field
Setpoint Name
R/W
Format
Value Definition
403019
0
0x0001
Demand Window Setpoint
R/W
Encoded
0 = Fixed
1 = Sliding
403020
7-0
0x00FF
Demand Interval
R/W
Unit: Minute (5 to 60 minutes)
403021
7-0
0x00FF
Breaker Health Alarm Threshold
R/W
Unit: Percentage (50 to 100)
403022
11-0
0x0FFF
System Voltage
R/W
Unit: Volt (208 to 690)
403023
0
0x0001
Neutral Transformer Style
R
Encoded
0 = Rogowski coil
1 = Current sensor
403024
0
0x0001
Ground Sensor Style
R
Encoded
0 = Rogowski coil
1 = Current sensor
Appendix A - Modbus Communication Port Setting