Table 3. Advanced Protection Features (PT25 only, unless specified additionally)
Protection
Unit
Setting
Note
Voltage Protection
Over-voltage Pickup
V
180-720 adjustable
Interval of 1
Over-voltage Delay
s
1~ 300 adjustable
Interval of 1
Under-voltage Pickup
V
60-670 adjustable
Interval of 1
Under- voltage Delay
s
1- 300 adjustable
Interval of 1
Voltage Unbalance Pickup
% V
5- 25 adjustable
Interval of 1
Voltage Unbalance Delay
s
1- 300 adjustable
Interval of 1
Current Protection
Current Unbalance Pickup
% A
5- 25 adjustable
Interval of 1
Current Unbalance Delay
s
1- 300 adjustable
Interval of 1
Phase Loss Pickup
% A
75
Phase Loss Delay
s
1- 240 adjustable
Interval of 1
Power Protection
Reverse Power Pickup
kW
1- 65500 adjustable
Interval of 1
Reverse Power Delay
s
1- 300 adjustable
Interval of 1
Frequency Protection
Over-frequency Pickup
Hz
40- 70 adjustable
Interval of 1
When Phase-A phase voltage
exceeds 100V, the frequency
metering will start
Over-frequency Delay
s
0.2- 5 adjustable
Interval of 0.1
Under-frequency Pickup
Hz
40- 70 adjustable
Interval of 1
Under-frequency Delay
s
0.2- 5 adjustable
Interval of 0.1
Phase Sequence Protection
Positive Sequence (A-B-C)
3-phase voltage sequence is the same as the
setting, and the trip unit acts
When all three phase voltages
exceed 100V, the phase sequence
metering will start
Reversed Sequence (A-C-B)
Demand Protection
Current Demand Pickup
x (I
n
)
0.2-1.0 adjustable
Interval of 0.1
PT20/25 supports this function
Current Demand Delay
s
15-1500 adjustable
Interval of 1
Power Demand Pickup
kW
1- 65500 adjustable
Interval of 1
Power Demand Delay
s
15-1500 adjustable
Interval of 1
2. Protection and Metering Features