4 Commissioning
4.10 Operation
34
DX-NET-ETHERCAT-2
01/14 MN040009EN
www.eaton.com
Device status
Error messages
Bit
Description
Value = 0
Value = 1
0
Drive not ready
ready for operation (READY)
1
stop
Operation (RUN)
2
Clockwise rotating field (FWD)
Anticlockwise rotating field (REV)
3
no error
Fault detected (FAULT)
4
Acceleration ramp
Frequency actual value equals setpoint
input
5
–
Zero speed
6
Speed control deactivated
Speed control activated
7
Not used
Failure code
[hex]
Value shown on
display
Meaning
00
no-fit
Stop, ready for operation
01
OI-b
Braking chopper overcurrent
02
OL-br
Braking resistance overload
03
O-l
• Overcurrent at variable frequency drive output
• Motor overload
• Overtemperature on variable frequency drive (heat sink)
04
I.t-trp
Motor, thermal overload
05
SAFE -1
Short-circuit at safety circuit input
06
O Volts
Overvoltage (DC link)
07
V-volts
undervoltage (DC link)
08
O-t
Overtemperature (heat sink)
09
V-t
Undertemperature (heat sink)
0A
P-dEf
Default settings, parameters have been loaded
0B
E-trip
External error message
0C
SC-ObS
Error, OP bus
0D
FLt-dc
Excessively large voltage waves in DC link
0E
P-LOSS
Phase failure (mains side)
0F
h O-I
Overcurrent at variable frequency drive output
10
th-Flt
Thermistor fault, built-in (heat sink)
11
dAtA-F
EEPROM checksum fault
12
4-20F
Analog input:
• out-of-range value
• Wire breakage (4 mA monitoring)
13
dAtA- E
Error in internal memory
14
V-dEF
User-definable factory parameters have been loaded