Modbus TCP On-Board Communications
28
PowerXL DG1 Series VFD
MN040010EN—May 2014 www.eaton.com
Process Data Out 1 to 8
Process Data Out values 1 to 8 can be used in application for
various purposes. See DG1 application manual for what
these values can be set to.
Process Data OUT (Slave
R
Master)
The fieldbus master can read the AFD’s actual values using
process data variables. Standard, Pump and Fan Control, PID
control and Multi-Purpose applications use process data as
follows.
Table 58. Process Data OUT
Process Data IN (Master
R
Slave)
Control Word, Reference and Process Data are used with
All-in-One applications as follows.
Table 59. Process Data IN
ID
Data
Value
Unit
Scale
2104
Process Data OUT 1
–32768~32767
—
—
2105
Process Data OUT 2
–32768~32767
—
—
2106
Process Data OUT 3
–32768~32767
—
—
2107
Process Data OUT 4
–32768~32767
—
—
2108
Process Data OUT 5
–32768~32767
—
—
2109
Process Data OUT 6
–32768~32767
—
—
2110
Process Data OUT 7
–32768~32767
—
—
2111
Process Data OUT 8
–32768~32767
—
—
ID
Data
Value
Unit
Scale
2003
Reference
Speed Reference
Hz
0.01
2001
Control Word
—
—
2004
Process Data IN1
Set point / Feedback / Feedforward for PID
%
0.01%
2005
Process Data IN2
Set point / Feedback / Feedforward for PID
%
0.01%
2006
Process Data IN3
Set point / Feedback / Feedforward for PID
%
0.01%
2007
Process Data IN4
Set point / Feedback / Feedforward for PID
%
0.0
1%
2008
Process Data IN5
Set point / Feedback / Feedforward for PID
%
0.0
1%
2009
Process Data IN6
Set point / Feedback / Feedforward for PID
%
0.0
1%
2010
Process Data IN7
Set point / Feedback / Feedforward for PID
%
0.0
1%
2011
Process Data IN8
Set point / Feedback / Feedforward for PID
%
0.0
1%
Содержание PowerXL DG1 Series VFD
Страница 1: ...PowerXL DG1 Series VFD Communication Manual Effective May 2014 New Information...
Страница 2: ......
Страница 92: ...BACnet MS TP On Board Communication 78 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com Fault Tracing...
Страница 122: ...PROFIBUS DP External Communication Cards 108 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 132: ...PROFIBUS DP External Communication Cards 118 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 148: ...Appendix A Parameter ID List 134 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 149: ...Appendix A Parameter ID List PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com 135...
Страница 150: ...Appendix A Parameter ID List 136 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 151: ......