EtherNet/IP On-Board Communications
PowerXL DG1 Series VFD
MN040010EN—May 2014 www.eaton.com
51
List of Services
The services supported by these object classes are shown below.
Table 70. Services Supported by Object Classes
List of Data Types
The attribute list that follows includes information on the data
type of each attribute. The following tables explain the data,
structure, and array type codes used in the data type column.
Following data types are supported.
Table 71. Elementary Data Types
Table 72. Constructed Data Types
Reset Service
The following table lists the different types of resets
supported by the identity object.
Resetting the PowerXL interface to its out-of-box
configuration will change the response of the drive to a loss
of communications with the PowerXL. The device will have
to be re-configured for your application before resuming
normal operation. Reset Time 1 sec.
Table 73. Different Types of Resets Supported
by the Identity Object
Service
Code
(in hex)
Service Name
Identity
Object
Connection
Manager
TCP/IP
Interface
Ethernet
Link
Assembly
Motor
Data
Control
Supervisor
AC/DC
Drive
Vendor
Parameter
Class
Inst
Class
Inst
Class
Inst
Class
Inst
Class
Inst
Class
Inst
Class
Inst
Class
Inst
Class
Inst
01
Get_Attributes_All
Y
Y
Y
Y
Y
Y
05
Reset (Type 0 & 1)
Y
Y
0E
Get_Attribute_Single
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
10
Set_Attribute_Single
Y
Y
Y
Y
Y
Y
4E
Forward Close
Y
52
Unconnected_Send
Y
54
Forward_Open
Y
Data Type
Name
Data Type
Code
(in hex)
Data Type Description
BOOL
C1
Logical Boolean with values TRUE and
FALSE
SINT
C2
Signed 8-bit integer value
INT
C3
Signed 16-bit integer value
USINT
C6
Unsigned 8-bit integer value
UINT
C7
Unsigned 16-bit integer value
UDINT
C8
Unsigned 32-bit integer value
BYTE
D1
Bit string–8-bit
WORD
D2
Bit string–16-bit
SHORT_STRING
DA
Character string (1 byte per
character,
1 byte length indicator)
REAL
CA
32-bit floating point value
SHORT_STRING
DA
Character string (1 byte per character, 1
byte length indicator)
Type Code
Description
A1
Abbreviated array type encoding
A2
Formal structure type encoding
Value
Type of Reset
0
Initializes drive to the Power-up state.
1
Writes default values to all instance attributes AND then saves
all non-volatile attributes to FLASH memory AND then
performs the equivalent of a Reset (0).
Содержание PowerXL DG1 Series VFD
Страница 1: ...PowerXL DG1 Series VFD Communication Manual Effective May 2014 New Information...
Страница 2: ......
Страница 92: ...BACnet MS TP On Board Communication 78 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com Fault Tracing...
Страница 122: ...PROFIBUS DP External Communication Cards 108 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 132: ...PROFIBUS DP External Communication Cards 118 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 148: ...Appendix A Parameter ID List 134 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 149: ...Appendix A Parameter ID List PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com 135...
Страница 150: ...Appendix A Parameter ID List 136 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 151: ......