Modbus TCP On-Board Communications
24
PowerXL DG1 Series VFD
MN040010EN—May 2014 www.eaton.com
Modbus Communication Standards
Example of the request to read coils 2000–2003 from Slave
device 18.
Table 37. Request to Read Coils
Example of the request to read Discrete Inputs 2000–2003
from Slave device 18.
Table 38. Request to Read Discrete Inputs
Example of the request to read Holding Registers 2000–2003
from Slave device 18.
Table 39. Request to Read Holding Registers
Example of the request to read Input Registers 2000–2003
from Slave device 18.
Table 40. Request to Read Input Registers
Example of the request to read exception status from Slave
device 18.
Table 41. Request to Read Exception Status
Example of Read Diagnostics from Slave address 18.
Table 42. Read Diagnostics
Item
Code
Description
Slave address
0x12
Function code
0x01
Start address High
0x07
Starting address 0x07D0 hex (= 2000)
Start address Low
0xD0
Number of coils High
0x00
Number of coils 0x0003 hex (= 3)
Number of coils Low
0x03
CRC High
0x7E
CRC Low
0x25
Item
Code
Description
Slave address
0x12
Function code
0x02
Start address High
0x07
Starting address 0x07D0 hex (= 2000)
Start address Low
0xD0
Number of Discrete
Inputs High
0x00
Number of Discrete Inputs
0x0003 hex (= 3)
Number of Discrete
Inputs Low
0x03
CRC High
0x3A
CRC Low
0x25
Item
Code
Description
Slave address
0x12
Function code
0x03
Start address High
0x07
Starting address 0x07D0 hex (= 2000)
Start address Low
0xD0
Number of Holding
Registers High
0x00
Number of Holding Registers
0x0003 hex (= 3)
Number of Holding
Registers Low
0x03
CRC High
0x07
CRC Low
0xE5
Item
Code
Description
Slave address
0x12
Function code
0x04
Start address High
0x07
Starting address 0x07D0 hex (= 2000)
Start address Low
0xD0
Number of Input
Registers High
0x00
Number of Input Registers
0x0003 hex (= 3)
Number of Input
Registers Low
0x03
CRC High
0xB2
CRC Low
0x25
Item
Code
Description
Slave address
0x12
Function code
0x07
CRC High
4C
CRC Low
D2
Item
Code
Description
Slave address
0x12
Function code
0x08
Sub function High
0x00
Sub function code 0x0000 (= 0)
Note. Only support sub function code
0x0000
Sub function Low
0x00
Data High
0xA5
Data 0xA5A5 (= 42405)
Data Low
0xA5
CRC High
0x59
CRC Low
0x83
Содержание PowerXL DG1 Series VFD
Страница 1: ...PowerXL DG1 Series VFD Communication Manual Effective May 2014 New Information...
Страница 2: ......
Страница 92: ...BACnet MS TP On Board Communication 78 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com Fault Tracing...
Страница 122: ...PROFIBUS DP External Communication Cards 108 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 132: ...PROFIBUS DP External Communication Cards 118 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 148: ...Appendix A Parameter ID List 134 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 149: ...Appendix A Parameter ID List PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com 135...
Страница 150: ...Appendix A Parameter ID List 136 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 151: ......