EtherNet/IP On-Board Communications
52
PowerXL DG1 Series VFD
MN040010EN—May 2014 www.eaton.com
Common Industrial Objects Implemented
by the PowerXL EIP
CIP Common Required Objects
Identity Object, Class 0x01
This object provides identification of and general information about the PowerXL.
Table 74. Identity Object
ID
Description
Data Type
Access Rule
Remarks/Default Values
Class Attributes
01h
Revision
UINT
Get
1
02h
Max Instances
UINT
Get
1
03h
Number of instances
UINT
Get
1
06h
Maximum ID Class Attribute
UINT
Get
7
07h
Maximum ID Instance Attribute
UINT
Get
7
Class Services
0Eh
Get_Attribute_Single
01h
Get_Attribute_All
Instance Attributes
01h
Vendor ID
UINT
Get
68 (Eaton Vendor ID)
02h
Device Type
UINT
Get
CIP specified–lined to motor (AC Drive)–2
03h
Product Code
UINT
Get
0x3000
04h
Revision
STRUCT of
Get
Major Revision
USINT
4
Minor Revision
USINT
3
05h
Status
WORD
Get
0x34–Default
06h
Serial Number
UDINT
Get
07h
Product Name
SHORT_STRING
Get
PowerXL
Instance Services
01h
Get_Attributes_All
05h
Reset
0Eh
Get_Attribute_Single
Содержание PowerXL DG1 Series VFD
Страница 1: ...PowerXL DG1 Series VFD Communication Manual Effective May 2014 New Information...
Страница 2: ......
Страница 92: ...BACnet MS TP On Board Communication 78 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com Fault Tracing...
Страница 122: ...PROFIBUS DP External Communication Cards 108 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 132: ...PROFIBUS DP External Communication Cards 118 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 148: ...Appendix A Parameter ID List 134 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 149: ...Appendix A Parameter ID List PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com 135...
Страница 150: ...Appendix A Parameter ID List 136 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 151: ......