EtherNet/IP On-Board Communications
PowerXL DG1 Series VFD
MN040010EN—May 2014 www.eaton.com
31
Figure 19. Module and Network Status
Module Status Indications
Represents the state of the drive.
Table 62. Module Status LED Description
1
Flash rate is 1 flash per second.
Network Status Indications
Represents the state of the Ethernet port network interface.
Table 63. Network Status LED Description
1
Flash rate is 1 flash per second.
Indicator State
Summary
Meaning
Steady Off
No power
No power is supplied to the PowerXL.
Steady Green
Device operational
PowerXL is operating correctly.
Flashing Green
1
Standby
PowerXL has not been configured.
Flashing Red
1
Minor fault
PowerXL has detected a recoverable minor fault.
Note. An incorrect or inconsistent configuration would be considered a minor fault.
Also check that on clearing the fault, it turns off.
Steady Red
Major fault
PowerXL has detected a non-recoverable major fault.
Flashing Green/Red
1
Self-test
PowerXL is performing its power up testing.
Module Status
Network Status
Indicator State
Summary
Meaning
Steady Off
Not powered, no IP address
PowerXL is powered off, or is powered on but with no IP address configured (Interface
Configuration attribute of the TCP/IP Interface Object).
Flashing Green
1
No connections
An IP address is configured, but no CIP connections are established, and an Exclusive Owner
connection has not timed out.
Steady Green
Connected
At least one CIP connection (any transport class) is established, and an
Exclusive Owner connection has not timed out.
Flashing Red
1
Connection timeout
PowerXL is powered on and an exclusive Owner connection has timed out. It returns to steady
green only when all timed out Exclusive Owner connections are established.
Steady Red
Major fault
PowerXL has detected a non-recoverable major fault.
Flashing Green/Red
1
Self-test
PowerXL is performing its power up testing.
Содержание PowerXL DG1 Series VFD
Страница 1: ...PowerXL DG1 Series VFD Communication Manual Effective May 2014 New Information...
Страница 2: ......
Страница 92: ...BACnet MS TP On Board Communication 78 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com Fault Tracing...
Страница 122: ...PROFIBUS DP External Communication Cards 108 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 132: ...PROFIBUS DP External Communication Cards 118 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 148: ...Appendix A Parameter ID List 134 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 149: ...Appendix A Parameter ID List PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com 135...
Страница 150: ...Appendix A Parameter ID List 136 PowerXL DG1 Series VFD MN040010EN May 2014 www eaton com...
Страница 151: ......