3 Installation
3.6 Electrical Installation
94
DC1 Variable Frequency Drive
04/16 MN04020003Z-EN
www.eaton.com
3.6.2.10 Control signal terminals IP66
In the case of DC1 variable frequency drives with an IP66 degree of
protection, the plug-in control signal terminals are located under the terminal
cover. In version DC1-…A6SN, the local controls will already be connected.
Figure 59: DC1-…A6SN (connection wired at the factory)
When supplied, the control signal terminals will be connected as follows:
Table 12: Configuration of the control signal terminals
When the device is set to its default settings, the setpoint value can be set
using the potentiometer. Meanwhile, the REV – 0 – FWD selector switch can
be used to set the drive’s operating direction (counterclockwise rotating field
mode – STOP – clockwise rotating field mode).
Pin
Color
Function
1
RD (red)
+24 V to FWD/REV selector switch
2
BU (blue)
From selector switch = FWD
3
YE (yellow)
From selector switch = REV
5
GN (green)
+10 V to potentiometer
6
WH (white)
From potentiometer = f-Set
7
BK (black)
0 V to potentiometer
REV
FWD
0
ON
OFF
PWR
1 2 3 4 5 6 7 8 9 10 11
U
V
W
L1/N L2/N
L3
⏚
⏚
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
+24 V
DI1
AI1
0 V
DI2
DI3
AO1
0 V
K13
K14
+10 V
BK
WH
GN
YE
BU
RD
Содержание PowerXL DC1
Страница 1: ...Manual PowerXL DC1 Variable Frequency Drives Installation Manual 04 16 MN04020003Z EN...
Страница 4: ...II...
Страница 114: ...3 Installation 3 9 Protection against electric shock 110 DC1 Variable Frequency Drive 04 16 MN04020003Z EN www eaton com...
Страница 176: ...7 Accessories 7 2 General accessories List 172 DC1 Variable Frequency Drive 04 16 MN04020003Z EN www eaton com...