7 Accessories
7.1 Device-specific accessories
DC1 Variable Frequency Drive
04/16 MN04020003Z-EN
www.eaton.com
169
Figure 91: Block diagram DXC-EXT-2RO1AO
Parameter Definition
P-18 = 1: READY, variable frequency drive ready for operation
Typical operating mode (DXC-EXT-2RO1AO control signal terminals):
•
12/13 closed
→
There is an enable signal for operation (FWD),
READY and RUN messages: Green indicator light, for example
•
10/11 closed
→
Error message (not READY):
Red indicator light, for example
DANGER
Dangerous voltage!
Expansion module DXC-EXT-2RO1AO must not be placed into
operation until all mounting and installation work has been
completed. Any other use will be considered to be an
inappropriate use.
2
DI1
3
DI2
4
DI3
1
5
+10 V
< 20 mA
6
7
0 V
0 V
8
9
10
11
12
13
1
DC1
2
3
4
5
6
8
9
10
11
P-18 = 1
READY
7
AI1
0 ... +10 V
AO1
0 ... +10 V/
20 mA
+24 V, <100 mA
f-Soll
f-Out
K1
K2
250 V AC/220 V DC, 1 A
4.7 kΩ
+
FWD
→
Parameter P-25 must be set to a value between 0 and 7 in order
for the output to function as a digital output.
If the parameter is set to a value greater than 7, relay output K2
will not work properly.
→
P-18 can also be used to select operating messages for the DC1
variable frequency drive’s internal relay (RO1).
Содержание PowerXL DC1
Страница 1: ...Manual PowerXL DC1 Variable Frequency Drives Installation Manual 04 16 MN04020003Z EN...
Страница 4: ...II...
Страница 114: ...3 Installation 3 9 Protection against electric shock 110 DC1 Variable Frequency Drive 04 16 MN04020003Z EN www eaton com...
Страница 176: ...7 Accessories 7 2 General accessories List 172 DC1 Variable Frequency Drive 04 16 MN04020003Z EN www eaton com...