6 Technical Data
6.8 Radio interference suppression filter
154
DC1 Variable Frequency Drive
04/16 MN04020003Z-EN
www.eaton.com
Table 29: Assigned radio interference suppression filter (single-phase)
Device Type
Size
Input
current
Radio interference suppression filter, single-phase
Max. mains voltage U
LN
: 250 V +0%, 50/60 Hz ±10%
Max. ambient temperature: 50
o
C
Part no.
rated
operational
current
Leakage
current
(IEC38, ±10 %)
Maximum motor cable length
based on RFI class
C1
C2
C3
I
LN
I
e
I
PE
l
l
l
A
A
mA
mA
mA
mA
Mains voltage 115 V
Supply voltage (50/60 Hz) U
LN
110 (-10 %) - 115 (+10 %) V
U
e
115 V AC, single-phase / U
2
230 V AC, three-phase (internal voltage doubler)
DC1-1D2D3NN-A20N
FS1
7.8
DX-EMC12-014-FS1
14
8
25
75
100
DC1-1D4D3NN-A20N
FS1
15.8
DX-EMC12-019-FS1
19
8
25
75
100
DC1-1D5D8NB-A20N
FS2
21.9
DX-EMC12-025-FS2
25
8
25
75
100
Mains voltage 230 V
Supply voltage (50/60 Hz) U
LN
200 (-10 %) - 240 (+10 %) V
U
e
230 V AC, single-phase / U
2
230 V AC, three-phase
DC1-122D3NN-A20N
FS1
3.7
DX-EMC12-014-FS1
14
8
25
75
100
DC1-124D3NN-A20N
FS1
7.5
DX-EMC12-014-FS1
14
8
25
75
100
DC1-127D0NN-A20N
FS1
12.9
DX-EMC12-014-FS1
14
8
25
75
100
DC1-127D0NB-A20N
FS2
12.9
DX-EMC12-025-FS2
25
8
25
75
100
DC1-12011NB-A20N
FS2
19.2
DX-EMC12-025-FS2
25
8
25
75
100
DC1-12015NB-A20N
FS3
29.2
DX-EMC12-031-FS3
31
8
25
75
100
Содержание PowerXL DC1