3 Installation
3.3 Mounting
DC1 Variable Frequency Drive
04/16 MN04020003Z-EN
www.eaton.com
61
The values specified in
Table 3 are recommended values for an ambient
temperature of up to +50 °C with an IP20 degree of protection or +40 °C
with an IP66 degree of protection, an installation altitude of up to 1,000 m,
and a switching frequency of up to 8 kHz.
→
Typical heat loss makes up about 3 % of the operational load
conditions.
①
Figure 26: Minimum required clearance
in front of the
variable frequency drive when installed in an
enclosure (control panel)
Size with IP20 degree of
protection
Minimum clearance
①
FS1, …, FS4
15 mm ( 0.59 inch)
FS1, …, FS4 with DX-NET-
SWD3 and SWD4-8SF2-5
50 mm ( 1.97 inch)