3 Installation
3.3 Mounting
DC1 Variable Frequency Drive
04/16 MN04020003Z-EN
www.eaton.com
63
3.3.3.2 Fixing on a mounting rail
As an alternative to screw fixing, DC1 variable frequency drives with sizes
FS1, FS2 and FS3 and a degree of protection of IP20 can also be mounted on
a mounting rail as per IEC/EN 60715.
Figure 28: Mounting rail conforming with IEC/EN 60715
▶
To do this, place the variable frequency drive on the mounting rail from
above [1] and press it down until it snaps into place [2].
Figure 29: Fixing on a mounting rail
→
If you use EMC mounting adapters (DX-EMC-MNT-…), use a tall
mounting rail (15 mm) preferably.
→
If you use EMC mounting adapters (DX-EMC-MNT-…), use a tall
mounting rail (15 mm) preferably.
35
1
7.5
15
1.38”
0.04”
0.29”
0.59”
2
1
VAR
EMC
VAR
EMC
Содержание PowerXL DC1